11.6.34.3Error35-2(emergencycode7304h)
Cause: ENC CH2 Resolver: error, encoder monitoring
Suggested steps:
Check encoder cables, voltage supply, and selection. Make sure unused channels
are switched off.
Theencoderisnot
connectedornotworking
properly.
l Ifthisisencoderhasanaloguesignals,please
checkthesignalamplitudevs.parameter
EncObsMin
l Checkcabling.Ifavailable,pleasetryanother
encoderandcable.
l Seedetailederrorinformation(>>)foramore
detaileddescription.
Thisissueisprobably
causedbyanunsuitable
parametersetting.
l Saveyourparametersetforalaterrestore.
l See'historyofparameterchanges'andundo
thelatestchanges.
l Pleasecheckyourparametersetfor
implausiblesettings.
l Pleasesetdevicetofactorysetting,restart,and
seeiftheerroroccursagain.
l Whenreportingthiserrortoyourservice
partner,pleaseincludeyourdevice's
parametersetting.
ID No.: 0842.26B.5-01Date: 09.2020
ServoOne- Device Help
422
11 Alarms & warnings
11.6.34.4Error35-3(emergencycode7307h)
Cause: ENC CH3 SinCos: error, encoder monitoring
Suggested steps:
Check encoder cables, voltage supply, and selection. Make sure unused channels
are switched off.
Theencoderisnot
connectedornotworking
properly.
l Ifthisisencoderhasanaloguesignals,please
checkthesignalamplitudevs.parameter
EncObsMin
l Checkcabling.Ifavailable,pleasetryanother
encoderandcable.
l Seedetailederrorinformation(>>)foramore
detaileddescription.
Thisissueisprobably
causedbyanunsuitable
parametersetting.
l Saveyourparametersetforalaterrestore.
l See'historyofparameterchanges'andundo
thelatestchanges.
l Pleasecheckyourparametersetfor
implausiblesettings.
l Pleasesetdevicetofactorysetting,restart,and
seeiftheerroroccursagain.
l Whenreportingthiserrortoyourservice
partner,pleaseincludeyourdevice's
parametersetting.