Overcurrent, Voltage, Synchronism Check, and Frequency Elements
Synchronism Check Elements (Not in SEL-351A-1)
In this example, the angular difference across the circuit breaker can be
greater for a manual close (25 degrees) than for an automatic reclose
(15 degrees).
A single output contact (e.g., OUT102 = CLOSE) can provide the close
function for both automatic reclosing and manual closing (see Figure 6.1 logic
output).