EasyManua.ls Logo

Schweitzer Engineering Laboratories SEL-351A - Setting Negative-Sequence Time-Overcurrent Elements; Figure F.1 Minimum Response Time Added to a Negative-Sequence Time-Overcurrent Element 51 QT

Schweitzer Engineering Laboratories SEL-351A
666 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
F.2
SEL-351A Relay Instruction Manual Date Code 20080213
Setting Negative-Sequence Overcurrent Elements
Setting Negative-Sequence Time-Overcurrent Elements
Setting Negative-Sequence Time-Overcurrent
Elements
Negative-sequence time-overcurrent element 51QT should not be set to trip
directly when it is set with a low time-dial setting 51QTD, that results in curve
times below 3 cycles (see curves in Figure 9.1Figure 9.10). This is because
negative-sequence current can transiently appear when a circuit breaker is
closed and balanced load current suddenly appears. Refer to Figure 3.21 for
more information on negative-sequence time-overcurrent element 51QT.
To avoid having negative-sequence time-overcurrent element 51QT with such
low time-dial settings trip for this transient negative-sequence current
condition, make settings similar to the following:
SV6PU = 1.50 cycles (minimum response time; transient condition lasts less
than 1.5 cycles)
SV6 = 51Q (run pickup of negative-sequence time-overcurrent element
51QT through SEL
OGIC control equation variable timer SV6)
TR = .. + 51QT * SV6T +.. (trip conditions; SV6T is the output of the
SEL
OGIC control equation variable timer SV6)
Figure F.1 Minimum Response Time Added to a Negative-Sequence Time-
Overcurrent Element 51QT
Continue reading in Coordinating Negative-Sequence Overcurrent Elements
on page F.3 for guidelines on coordinating negative-sequence time-
overcurrent elements and for a coordination example.
51QT * SV6T
I (3I
2
)51Q
SV6PU
t
Courtesy of NationalSwitchgear.com

Table of Contents