Date Code 20080213 Instruction Manual SEL-351A Relay
Appendix L
SEL Synchrophasors
Overview
The SEL-351A provides Phasor Measurement Control Unit (PMCU)
capabilities when connected to an IRIG-B time source with an accuracy of
±10 μs or better. Synchrophasor data are available via the MET PM ASCII
command and the SEL Fast Message Unsolicited Write message.