EasyManua.ls Logo

Schweitzer Engineering Laboratories SEL-351A - Figure 5.4 Seal-In of Breaker Failure Occurrence for Message Display

Schweitzer Engineering Laboratories SEL-351A
666 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5.13
Date Code 20080213 Instruction Manual SEL-351A Relay
Trip and Target Logic
Front-Panel Target LEDS
Other Applications for the {TARGET RESET/LAMP TEST} Function
Refer to the bottom of Figure 5.1. The combination of the {TARGET RESET}
pushbutton and the TAR R (Target Reset) serial port command is available as
Relay Word bit TRGTR. Relay Word bit TRGTR pulses to logical 1 for one
processing interval when either the {TARGET RESET} pushbutton is pushed or the
TAR R (Target Reset) serial port command is executed.
Relay Word bit TRGTR can be used to unlatch logic. For example, refer to the
breaker failure logic in Figure 7.25. If a breaker failure trip occurs (SV7T
asserts), the occurrence can be displayed on the front panel with seal-in logic
and a rotating default display (see Rotating Default Display (Only on Models
With LCD) on page 7.34 and Rotating Default Display on page 11.12):
SV8 = (SV8 + SV7T) * !TRGTR
DP3 = SV8
DP3_1 = BREAKER FAILURE
DP3_0 = NA (blank)
Figure 5.4 Seal-in of Breaker Failure Occurrence for Message Display
If a breaker failure trip has occurred, the momentary assertion of SV7T
(breaker failure trip) will cause SV8 in Figure 5.4 to seal-in. Asserted SV8 in
turn asserts DP3, causing the message:
to display in the rotating default display.
This message can be removed from the display rotation by pushing the
{TARGET RESET} pushbutton (Relay Word bit TRGTR pulses to logical 1,
unlatching SV8 and in turn deasserting DP3). Thus, front-panel rotating
default displays can be easily reset along with the front-panel targets by
pushing the {TARGET RESET} pushbutton.
SELOGIC Control
Equation Setting
FAULT
SELOGIC control equation setting FAULT has control over or is used in the
following:
Front-panel target LEDs INST, A, B, and C. See Front-Panel
Target LEDS on page 5.10.
Demand MeteringFAULT is used to suspend demand
metering peak recording. See Demand Metering on page 8.20.
Maximum/Minimum MeteringFAULT is used to block
Maximum/Minimum metering updating. See Maximum/
Minimum Metering on page 8.29.
SV7T
Breaker Failure Trip
(= logical 1)
(= logical 0)
Target Reset
TRGTR
SV8
DP3 = SV8
DP3_1 = BREAKER FAILURE
DP3_0 = (blank)
BREAKER FAILURE
NOTE: Display Points are only
available on relay models with an LCD.
Courtesy of NationalSwitchgear.com

Table of Contents