A.2
SEL-351A Relay Instruction Manual Date Code 20080213
Firmware and Manual Versions
Firmware
This firmware differs from the previous version as follows:
SEL-351A-R401-V0-Z008006-D20070725
Corrected problem that caused intermittent 50G element opera-
tion. The problem only manifests on systems with load current
very near nominal current and with high harmonic content.
20070725
This firmware differs from the previous version as follows:
SEL-351A-R400-V0-Z008006-D20070117
Protection
Added support for new SEL Fast Message Synchrophasor pro-
tocol, event reporting, and metering.
Reporting
Changed default event report and compressed event report com-
mand length to follow Global Setting LER.
Communications
Lowered Port 1 maximum speed from 38.4 kbps to 19.2 kbps.
20070117
This firmware differs from the previous version as follows:
SEL-351A-R112-V0-Z007005-D20060717
Corrected negative-sequence directional element operation for
delta systems when Z1ANG is set low.
Improved fault targeting for lightly loaded ungrounded systems.
Added Z0MTA setting to allow use of Best Choice Ground
Directional Element logic on systems with a neutral earth
resistor.
20060717
This firmware applies to the manual date code listed:
SEL-351A-R110-V0-Z006005-D20041210
Manual update only. See Table A .3. 20050518
This firmware differs from the previous version as follows:
SEL-351A-R110-V0-Z006005-D20041210
Added E79 setting options for enhanced recloser supervision
applications.
20041210
Allow phase and negative-sequence time overcurrent element
pickups to be set more sensitively.
Improve accuracy of voltage elements.
Improve password security.
Remove (*) indication of max current from raw event report.
Allow Z1ANG and Z0ANG settings to be set as low as
5degrees.
Power Factor values found in DNP and ASCII communication
now match in resolution when polled simultaneously.
Improved the timing of the setting group Relay Word Bit SGn to
update after a settings group change instead of during.
DNP event report now uses peak values instead of cosine-fil-
tered values when an event is triggered by the Adaptive Over-
current Element.
Improved the voltage scaling in the loss-of-potential (LOP)
logic.
DNPE was improved to automatically refresh all stored values
upon any DNPE settings change.
Improved initialization of communication ports when changing
protocols.
Setting PSTDLY in DNP setting to 0 time delay was improved
to end communications faster.
This firmware differs from the previous version as follows:
Table A.1 SEL-351A Firmware Revision History (Sheet 2 of 5)
Firmware Part/Revision No. Description of Firmware
Manual Date
Code
Courtesy of NationalSwitchgear.com

Table of Contents