7.41
Date Code 20080213 Instruction Manual SEL-351A Relay
Inputs, Outputs, Timers, and Other Control Logic
Rotating Default Display (Only on Models With LCD)
Extra Details for Displaying Metering Values on the Rotating Default
Display
Table 7.8 lists all the available metering values that rotate on the default
display, subject to the number of available display points. These values
correspond to the primary metering values available via the METER
command (MET [Instantaneous], MET X [Extended Instantaneous], MET D
[Demand], and MET E [Energy]; see Section 10: Serial Port Communications
and Commands for serial port commands).
Note in Table 7.8 that many of the magnitude values are listed with three
digits behind the decimal point. For example, the first value in Table 7.8 is
shown generically as in this example:
Magnitudes less than 10 display with three digits behind the decimal point:
Magnitudes greater than or equal to 10 display with two or fewer digits behind
the decimal point:
:IAPK
::IBPJ
IA= x.xxxA yyy˚
IA= 8.372A 0˚
IA= 52.37A 0˚
IB= 635.8A -120˚
IC= 1173A 120˚
Table 7.8 Mnemonic Settings for Metering on the Rotating Default Display (Sheet 1 of 4)
Mnemonic Display Description
IA I A =xx . xxxA yyyº IA input current
IB I B =xx.xxxA yyyº IB input current
IC I C =xx.xxxA yyyº IC input current
IN I N =xx . xxxA yyyº IN input current
VA
a
V A =x . xxxkV yyyº VA input voltage
VB
a
V B =x . xxxkV yyyº VB input voltage
VC
a
V C =x . xxxkV yyyº VC input voltage
VS V S =x. xxxkV yyyº VS input voltage (not in SEL-351A-1)
IG I G =xx . xxxA yyyº IG = IA + IB + IC (residual current)
3I0 3 I 0 =xx . xxxA yyyº 3I0 = IG (zero-sequence current)