EasyManua.ls Logo

Schweitzer Engineering Laboratories SEL-351A - Figure 2.8 Broken-Delta Secondary Connection to Voltage Input VS, Wye-Connected Pts

Schweitzer Engineering Laboratories SEL-351A
666 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2.16
SEL-351A Relay Instruction Manual Date Code 20080213
Installation
Making Rear-Panel Connections
Polarity Check for VSCONN = 3V0
Refer to Figure 2.8 (wye-connected PTs) or Figure 2.10 (open-delta
connected PTs). With setting VSCONN = 3V0, voltage input VS-NS expects
3V
0
voltage (V
S
= 3V
0
= V
A
+ V
B
+ V
C
) with the polarity shown. However, in
a nonfault, balanced system condition, voltage V
S
= 3V
0
0. The result is that
a polarity problem with voltage input VS-NS, such as when secondary wires are
on the wrong terminals, will not necessarily be apparent until a ground fault
occurs or testing is performed.
Wye-Connected PT Example
Figure 2.8 Broken-Delta Secondary Connection to Voltage Input VS, Wye-
Connected PTs
To verify the correct polarity on voltage input VS-NS, perform the following
test on the primary side of one of the PTs connected in broken-delta secondary
(refer to Figure 2.8) and observe the resultant voltage phase angle differences:
Open circuit the primary side of the PT connected to power system
phase A. With the resultant collapse of secondary voltage V
A
(V
A
= 0) in
the broken-delta secondary circuit, the voltage at voltage input VS-NS is:
V
S
= 3V
0
= V
A
+ V
B
+ V
C
= V
B
+ V
C
Figure 2.9 shows the resultant voltage V
S
, with respect to the wye-
connected power system voltages connected to the voltage inputs
VA-VB-VC-N (ABC rotation used in this example). For this scenario of the
VS
NS
Setting
VSCONN = 3V0
Open Circuit
for Test
VB
N
Setting
PTCONN = WYE
AB
C
VA
V
AN
V
BN
V
CN
VC
Step-Down
Transformer
SEL-351 Relay
Broken-Delta
Wye
V
A
V
B
V
S
V
C
Courtesy of NationalSwitchgear.com

Table of Contents