H.9
Date Code 20080213 Instruction Manual SEL-351A Relay
Distributed Network Protocol
Object Table
Object Table
The supported object, function, and qualifier code combinations are given by
Table H.5.
Table H.5 SEL-351A DNP Object Table (Sheet 1 of 5)
Object Request
a
Response
b
Obj Var Description
Func.
Codes
c
Qual.
Codes
d
Func.
Codes
c
Qual.
Codes
d
1 0 Binary Input—All Variations 1 0,1,6,7,8
1 1 Binary Input 1 0,1,6,7,8 129 0,1,7,8
12
e
Binary Input with Status 1 0,1,6,7,8 129 0,1,7,8
2 0 Binary Input Change—All Varia-
tions
1 6,7,8
2 1 Binary Input Change without
Time
1 6,7,8 129 17,28
2 2
e
Binary Input Change with Time 1 6,7,8 129,130 17,28
2 3 Binary Input Change with Rela-
tive Time
1 6,7,8 129 17,28
10 0 Binary OutputAll Variations 1 0,1,6,7,8
10 1 Binary Output
10 2
e
Binary Output Status 1 0,1,6,7,8 129 0,1
12 0 Control Block—All Variations
12 1 Control Relay Output Block 3,4,5,6 17,28 129 echo of
request
12 2 Pattern Control Block
12 3 Pattern Mask
20 0 Binary Counter—All Variations 1 0,1,6,7,8
20 1 32-Bit Binary Counter
20 2 16-Bit Binary Counter
20 3 32-Bit Delta Counter
20 4 16-Bit Delta Counter
20 5 32-Bit Binary Counter without
Flag
1 0,1,6,7,8 129 0,1,7,8
20 6
e
16-Bit Binary Counter without
Flag
1 0,1,6,7,8 129 0,1,7,8
20 7 32-Bit Delta Counter without
Flag
20 8 16-Bit Delta Counter without
Flag
21 0 Frozen Counter—All Variations
21 1 32-Bit Frozen Counter
21 2 16-Bit Frozen Counter
21 3 32-Bit Frozen Delta Counter
21 4 16-Bit Frozen Delta Counter
Courtesy of NationalSwitchgear.com