4.28
SEL-351A Relay Instruction Manual Date Code 20080213
Loss-of-Potential, Load Encroachment, and Directional Element Logic
Directional Control for Neutral-Ground and Residual-Ground Overcurrent Elements (Not in SEL-351A-1)
q From Figure 4.15; w Figure 3.19; e Figure 3.10.
Figure 4.17 Direction Forward/Reverse Logic for Residual-Ground
Overcurrent Elements
Level
Direction
Settings
Directional
Control
32GF
q
DIR1 = F
DIR1 = N
Relay
Word
Bits
to Residual Ground
Time-0vercurrent
Elements
w
to Residual Ground
Instantaneous/
Definite-Time
Overcurrent
Elements
e
ORDER = OFF
or
ORDER = P
Setting
Forward
Forward
32GR
q
Reverse
Level 1
DIR1 = R
Reverse
DIR2 = F
DIR2 = N
Forward
Level 2
DIR2 = R
Reverse
DIR3 = F
DIR3 = N
Forward
Level 3
DIR3 = R
Reverse
DIR4 = F
DIR4 = N
Forward
Level 4
DIR4 = R
Reverse