4.21
Date Code 20080213 Instruction Manual SEL-351A Relay
Loss-of-Potential, Load Encroachment, and Directional Element Logic
Directional Control for Neutral-Ground and Residual-Ground Overcurrent Elements (Not in SEL-351A-1)
q From Ta b le 4 .2; w to Figure 4.15 and Figure 4.16.
Figure 4.9 Negative-Sequence Voltage-Polarized Directional Element for
Neutral-Ground and Residual-Ground Overcurrent Elements
I
2
V
2
If Z2F Setting > 0, Forward Threshold = 1.25 • Z2F — 0.25 •
I
2
V
2
If Z2F Setting ≤ 0, Forward Threshold = 0.75 • Z2F — 0.25 •
Forward Threshold:
I
2
V
2
If Z2R Setting < 0, Reverse Threshold = 1.25 • Z2R + 0.25 •
I
2
V
2
If Z2R Setting ≥ 0, Reverse Threshold = 0.75 • Z2R + 0.25 •
Reverse Threshold:
Note: 1∠Z1L = One Ohm at the Positive-Sequence Line Angle
Direction Element Characteristics
R2
X2
Forward Threshold
Reverse Threshold
Z2 PLANE
32QGE is highest
w
R32QG
(Reverse)
F32QG
(Forward)
Best Choice
Ground
Directional
Logic
50QF
Enable
Forward
Threshold
32QGE
Reverse
Threshold
50QR
q
Re[V
2
•(I
2
•1
∠
Z1L)*]
|I
2
|
2
Z2 =
I
2
V
2
Relay
Word
Bits
Relay
Word
Bit
Relay
Word
Bit
Relay
Word
Bit
choice that is asserted