SEL-351A Relay Instruction Manual Date Code 20080213
Overcurrent, Voltage, Synchronism Check, and Frequency Elements
Frequency Elements
With these settings:
81D1P NFREQ
the overfrequency part of frequency element 1 logic is enabled. 81D1 and
81D1T operate as overfrequency elements. 81D1 is used in testing only.
Underfrequency Element
For example, make settings:
NFREQ = 60 Hz (nominal system frequency is 60 Hz)
E81 2 (enable frequency element 2)
81D2P = 59.65 Hz (frequency element 2 pickup)
With these settings:
81D2P < NFREQ
the underfrequency part of frequency element 2 logic is enabled. 81D2 and
81D2T operate as underfrequency elements. 81D2 is used in testing only.
Frequency Element
Operation
Refer to Figure 3.32.
Overfrequency Element Operation
With the previous overfrequency element example settings, if system
frequency is less than or equal to 61.25 Hz (81D1P = 61.25 Hz), frequency
element 1 outputs:
81D1 = logical 0 (instantaneous element)
81D1T = logical 0 (time delayed element)
If system frequency is greater than 61.25 Hz (81D1P = 61.25 Hz), frequency
element 1 outputs:
81D1 = logical 1 (instantaneous element)
81D1T = logical 1 (time delayed element)
Relay Word bit 81D1T asserts to logical 1 only after time delay 81D1D.
Underfrequency Element Operation
With the previous underfrequency element example settings, if system
frequency is less than or equal to 59.65 Hz (81D2P = 59.65 Hz), frequency
element 2 outputs:
81D2 = logical 1 (instantaneous element)
81D2T = logical 1 (time delayed element)
Relay Word bit 81D2T asserts to logical 1 only after time delay 81D2D.
If system frequency is greater than 59.65 Hz (81D2P = 59.65 Hz), frequency
element 2 outputs:
81D2 = logical 0 (instantaneous element)
81D2T = logical 0 (time delayed element)