EasyManua.ls Logo

Schweitzer Engineering Laboratories SEL-351A - Page 182

Schweitzer Engineering Laboratories SEL-351A
666 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4.56
SEL-351A Relay Instruction Manual Date Code 20080213
Loss-of-Potential, Load Encroachment, and Directional Element Logic
Directional Control Settings (Not in SEL-351A-1)
Ungrounded/High-Impedance Grounded System Considerations for
Setting E32IV
On ungrounded/high-impedance grounded systems (when setting
ORDER = U), phase-to-phase or unbalanced three-phase faults can cause the
ungrounded/high-impedance grounded element to operate on false quantities.
To prevent this situation, SEL
OGIC setting E32IV may be used as follows:
E32IV = V1GOOD * !32QE
The V1GOOD Relay Word bit (see Figure 4.1) deasserts during a three-phase
fault, and the 32QE Relay Word bit (see Figure 4.6) asserts during a phase-to-
phase fault. If either one of these occur, the E32IV setting evaluates to
logical 0, and the ungrounded/high-impedance grounded directional element
is blocked (see Figure 4.8).
When a switch or breaker closes, the poles can close sequentially (not at the
same time), creating a momentary current unbalance condition. To avoid any
possible operation of the ungrounded/ high-impedance grounded element for
this momentary current unbalance condition, set 3PO (three-pole open
condition; see Figure 5.3) in SEL
OGIC setting E32IV as follows:
E32IV = … + !3PO (= … + NOT[3PO])
The 3PO dropout time (setting 3POD) provides the extended blocking (3PO =
logical 1; !3PO = logical 0) for this momentary current unbalance condition.
Courtesy of NationalSwitchgear.com

Table of Contents