B.3 Parameter Table
508 YASKAWA ELECTRIC SIEP C710616 27G YASKAWA AC Drive A1000 Technical Manual
T2: PM Motor Auto-Tuning
T1-04
(704H)
Motor Rated Current
Sets the motor rated current as specified on the motor nameplate.
Default:
<6>
Min: 10% of drive rated
current
Max: 200% of drive
rated current
128
T1-05
(705H)
Motor Base Frequency
Sets the rated frequency of the motor as specified on the motor nameplate.
Default: 50.0 Hz
Min: 0.0 Hz
Max: 400.0 Hz
128
T1-06
(706H)
Number of Motor Poles
Sets the number of motor poles as specified on the motor nameplate.
Default: 4
Min: 2
Max: 48
129
T1-07
(707H)
Motor Base Speed
Sets the rated speed of the motor as specified on the motor nameplate.
Default: 1450 min
-1
Min: 0 min
-1
Max: 24000 min
-1
129
T1-08
(708H)
PG Number of Pulses Per
Revolution
Set the number of pulses per revolution for the PG being used (pulse generator or encoder).
Default: 1024 ppr
Min: 0 ppr
Max: 60000 ppr
129
T1-09
(709H)
Motor No-Load Current
(Stationary Auto-Tuning)
Sets the no-load current for the motor.
After setting the motor capacity to T1-02 and the motor rated current to T1-04, this parameter
will automatically display the no-load current for a standard 4 pole YASKAWA motor. Enter the
no-load current as indicated on the motor test report.
Default: –
Min: 0 A
Max: T1-04
129
T1-10
(70AH)
Motor Rated Slip
(Stationary Auto-Tuning)
Sets the motor rated slip.
After setting the motor capacity to T1-02, this parameter will automatically display the motor
slip for a standard 4 pole YASKAWA motor. Enter the motor slip as indicated on the motor test
report.
Default: –
Min: 0.00 Hz
Max: 20.00 Hz
129
T1-11
(70BH)
Motor Iron Loss
Sets the iron loss for determining the Energy Saving coefficient.
The value is set to E2-10 (motor iron loss) set when the power is cycled. If T1-02 is changed, a
default value appropriate for the motor capacity that was entered will appear.
Default: 14 W
<38>
Min: 0 W
Max: 65535 W
129
<6> Default setting value varies by the drive model (o2-04).
<9> Default setting value is dependent on the drive model (o2-04) and the Drive Duty (C6-01).
<10> Default setting is determined by the control mode (A1-02).
<18> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
<37> The availability of certain Auto-Tuning methods depends on the control mode selected for the drive.
<38> Default setting value differs depending on the motor code value and motor parameter settings.
No. (Addr.) Name Description Setting Page
T2-01
(750H)
<37>
PM Motor Auto-Tuning Mode
Selection
0: PM Motor Parameter Settings
1: PM Stationary Auto-Tuning
2: PM Stationary Auto-Tuning for Stator Resistance
3: Z Pulse Offset Tuning
8: Inertia Tuning
9: ASR Gain Auto-Tuning
11: Back EMF Constant Tuning
13: High Frequency Injection Parameter Tuning
14: PM Rotational Auto-Tuning
Note: 1.The settings of 13 and 14 are not available for models CIMR-A4A0930 and 4A1200.
2. Inertia Tuning and ASR Gain Auto-Tuning might not be available if gears are between
the machine and the motor shaft.
3. For special-purpose motors, YASKAWA recommends Back EMF Constant Tuning
after Stationary Auto-Tuning has been performed. Back EMF Constant Tuning rotates
the motor to measure the actual induction voltage constants, and therefore allows for
more accurate control than Stationary Auto-Tuning alone.
Default: 0
Min: 0
Max: 3, 8, 9, 11,13,
14
<10>
130
T2-02
(751H)
PM Motor Code Selection
Enter the motor code when using a YASKAWA PM motor. Once the motor code is entered, the
drive automatically sets parameters T2-03 through T2-09. Set T2-10 through T2-14 from the
values on the motor nameplate or from the motor test report. When using a motor that is not
supported motor code or a non-YASKAWA motor, set FFFF here and then adjust the other T2
parameters according the motor nameplate or the motor test report.
Default:
<16>
Min: 0000
Max: FFFF
130
No. (Addr.) Name Description Setting Page
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV

Table of Contents

Other manuals for YASKAWA A1000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA A1000 and is the answer not in the manual?

YASKAWA A1000 Specifications

General IconGeneral
TypeAC Drive
SeriesA1000
Input Voltage200-240V, 380-480V
Frequency Range0-400 Hz
Horsepower Range0.5 to 1000 HP
Power Range0.4 to 630 kW
Control MethodV/f Control
Overload Capacity150% for 60 seconds
BrakingDynamic Braking
CommunicationModbus
SafetySafe Torque Off (STO)
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheat
Operating Temperature-10 to +50°C
Storage Temperature-20 to 60°C
Humidity5 to 95% RH (non-condensing)
EnclosureIP20