B.6 Defaults by Drive Model Selection (o2-04) and ND/HD (C6-01)
YASKAWA ELECTRIC SIEP C710616 27G YASKAWA AC Drive A1000 Technical Manual 525
Parameter List
B
C5-17 (C5-37) Motor Inertia
kgm
2
0.273 0.333 0.333 0.490 0.49 0.90
C6-02Carrier Frequency Selection 171717
E2-01 (E4-01) Motor Rated Current A 131 160 160 190 190 260
E2-02 (E4-02) Motor Rated Slip Hz 1.33 1.6 1.6 1.43 1.43 1.39
E2-03 (E4-03) Motor No-Load Current A 38.2 44 44 45.6 45.6 72
E2-05 (E4-05) Motor Line to Line Resistance 0.039 0.03 0.03 0.022 0.022 0.023
E2-06 (E4-06) Motor Leakage Inductance % 18.8 20.2 20.2 20.5 20.5 20
E2-10 (E4-10) Motor Iron Loss for Torque Compensation W 823 852 852 960 960 1200
E5-01 Motor Code Selection (for PM Motors) Hex. 1213 1213 1214 1214 1215 1215
L2-02Momentary Power Loss Ride-Thru Times222222
L2-03 Momentary Power Loss Minimum Baseblock Time s 1.1 1.2 1.2 1.3 1.3 1.5
L2-04Momentary Power Loss Voltage Recovery Times0.611111
L3-24 Motor Acceleration Time for Inertia Calculations s 0.32 0.387 0.387 0.317 0.317 0.533
L8-02 Overheat Alarm Level C 130 130 125 125 115 115
L8-35 Installation Method Selection 0 00000
L8-38Carrier Frequency Reduction Selection 222222
n1-03 Hunting Prevention Time Constant ms 10 10 10 10 10 10
n5-02 Motor Acceleration Time s 0.32 0.387 0.387 0.317 0.317 0.533
<66> This parameter is available in models CIMR-A4A0930 and 4A1200.
No.
<66> This parameter is available in models CIMR-A4A0930 and 4A1200.
Name Unit Default Settings
Model CIMR-A 2A0312 2A0360 2A0415
C6-01 Drive Duty Selection
HD ND HD ND HD ND
0 1 0 1 0 1
o2-04 Drive Model Selection Hex. 76 77 78
E2-11 (E4-11) Motor rated Output kW 75 90 90 110 110 110
b3-04 V/f Gain during Speed Search % 80 80 80 80 80 80
b3-06 Output Current 1 during Speed Search 0.7 0.7 0.7 0.7 0.7 0.7
b3-07 <66>
Output Current 2 during Speed Search (Speed
Estimation Type)
––––––
b3-08
Current Control Gain during Speed Search (Speed
Estimation Type)
0.5 0.5 0.5 0.5 0.5 0.5
b3-26
<66> Start Speed Search Select ––––––
b8-03 Energy Saving Control Filter Time Constant s 2.00 2.00 2.00 2.00 2.00 2.00
b8-04 Energy Saving Coefficient Value 23.1 20.65 20.65 18.12 18.12 18.12
C5-17 (C5-37) Motor Inertia
kgm
2
0.90 1.10 1.10 1.90 1.90 1.90
C6-02Carrier Frequency Selection 171717
E2-01 (E4-01) Motor Rated Current A 260 260 260 260 260 260
E2-02 (E4-02) Motor Rated Slip Hz 1.39 1.39 1.39 1.39 1.39 1.39
E2-03 (E4-03) Motor No-Load Current A 72 72 72 72 72 72
E2-05 (E4-05) Motor Line to Line Resistance 0.023 0.023 0.023 0.023 0.023 0.023
E2-06 (E4-06) Motor Leakage Inductance % 20 20 20 20 20 20
E2-10 (E4-10) Motor Iron Loss for Torque Compensation W 1200 1200 1200 1200 1200 1200
E5-01 Motor Code Selection (for PM Motors) Hex. 1216 1216 FFFF FFFF FFFF FFFF
L2-02Momentary Power Loss Ride-Thru Times222222
L2-03 Momentary Power Loss Minimum Baseblock Time s 1.5 1.5 1.5 1.7 1.7 1.7
L2-04Momentary Power Loss Voltage Recovery Times111111
L3-24 Motor Acceleration Time for Inertia Calculations s 0.533 0.592 0.592 0.646 0.646 0.646
L8-02 Overheat Alarm Level C 120 120 120 120 120 120
L8-35 Installation Method Selection 0 00000
L8-38Carrier Frequency Reduction Selection 222222
n1-03 Hunting Prevention Time Constant ms 10 10 100 100 100 100
n5-02 Motor Acceleration Time s 0.533 0.592 0.592 0.646 0.646 0.646
No. Name Unit Default Settings
Model CIMR-A 2A0169 2A0211 2A0250
C6-01 Drive Duty Selection
HD ND HD ND HD ND
0 1 0 1 0 1
o2-04 Drive Model Selection Hex. 73 74 75
E2-11 (E4-11) Motor rated Output kW 37 45 45 55 55 75