B.6 Defaults by Drive Model Selection (o2-04) and ND/HD (C6-01)
YASKAWA ELECTRIC SIEP C710616 27G YASKAWA AC Drive A1000 Technical Manual 527
L8-38 Carrier Frequency Reduction Selection –22222222
n1-03 Hunting Prevention Time Constant ms 10 10 10 10 10 10 10 10
n5-02 Motor Acceleration Time s 0.145 0.154 0.154 0.168 0.168 0.175 0.175 0.265
<66> This parameter is available in models CIMR-A4A0930 and 4A1200.
No.
<66> This parameter is available in models CIMR-A4A0930 and 4A1200.
Name Unit Default Settings
Model CIMR-A – 4A0031 4A0038 4A0044 4A0058
C6-01 Drive Duty Selection –
HD ND HD ND HD ND HD ND
0 1 0 1 0 1 0 1
o2-04 Drive Model Selection Hex. 9C 9D 9E 9F
E2-11 (E4-11) Motor rated Output kW 11 15 15 18.5 18.5 22 22 30
b3-04 V/f Gain during Speed Search % 100 100 100 100 100 100 100 100
b3-06 Output Current 1 during Speed Search – 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
b3-07 <66>
Output Current 2 during Speed Search (Speed
Estimation Type)
–––––––––
b3-08
Current Control Gain during Speed Search (Speed
Estimation Type)
– 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
b3-26
<66> Start Speed Search Select – – – – – – – – –
b8-03 Energy Saving Control Filter Time Constant s 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50
b8-04 Energy Saving Coefficient Value – 140.88 126.26 126.26 115.74 115.74 103.58 103.58 92.54
C5-17 (C5-37) Motor Inertia
kgm
2
0.053 0.076 0.076 0.138 0.138 0.165 0.165 0.220
C6-02 Carrier Frequency Selection – 1 7 1 7 1 7 1 7
E2-01 (E4-01) Motor Rated Current A 19.9 26.5 26.5 32.9 32.9 38.6 38.6 52.3
E2-02 (E4-02) Motor Rated Slip Hz 1.7 1.6 1.6 1.67 1.67 1.7 1.7 1.8
E2-03 (E4-03) Motor No-Load Current A 5.6 7.6 7.6 7.8 7.8 9.2 9.2 10.9
E2-05 (E4-05) Motor Line to Line Resistance 0.922 0.55 0.55 0.403 0.403 0.316 0.316 0.269
E2-06 (E4-06) Motor Leakage Inductance % 19.6 17.2 17.2 20.1 20.1 23.5 23.5 20.7
E2-10 (E4-10) Motor Iron Loss for Torque Compensation W 385 440 440 508 508 586 586 750
E5-01 Motor Code Selection (for PM Motors) Hex. 123D 123D 123E 123E 123F 123F 1240 1240
L2-02 Momentary Power Loss Ride-Thru Time s 2 2 2 2 2 2 2 2
L2-03 Momentary Power Loss Minimum Baseblock Time s 0.9 1 1 1 1 1 1 1.1
L2-04 Momentary Power Loss Voltage Recovery Time s 0.3 0.6 0.6 0.6 0.6 0.6 0.6 0.6
L3-24 Motor Acceleration Time for Inertia Calculations s 0.265 0.244 0.244 0.317 0.317 0.355 0.355 0.323
L8-02 Overheat Alarm Level C 120 120 120 120 115 115 120 120
L8-35 Installation Method Selection – 2 2 2 2 2 2 0 0
L8-38 Carrier Frequency Reduction Selection –22222222
n1-03 Hunting Prevention Time Constant ms 10 10 10 10 10 10 10 10
n5-02 Motor Acceleration Time s 0.265 0.244 0.244 0.317 0.317 0.355 0.355 0.323
No. Name Unit Default Settings
Model CIMR-A – 4A0072 4A0088 4A0103 4A0139
C6-01 Drive Duty Selection –
HD ND HD ND HD ND HD ND
0 1 0 1 0 1 0 1
o2-04 Drive Model Selection Hex. A1 A2 A3 A4
E2-11 (E4-11) Motor rated Output kW 30 37 37 45 45 55 55 75
b3-04 V/f Gain during Speed Search % 100 100 100 100 100 80 80 60
b3-06 Output Current 1 during Speed Search – 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.7
b3-07 <66>
Output Current 2 during Speed Search (Speed
Estimation Type)
–––––––––
b3-08
Current Control Gain during Speed Search (Speed
Estimation Type)
– 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.8
b3-26
<66> Start Speed Search Select – – – – – – – – –
b8-03 Energy Saving Control Filter Time Constant s 0.50 0.50 0.50 0.50 0.50 2.00 2.00 2.00
b8-04 Energy Saving Coefficient Value – 92.54 76.32 76.32 71.56 71.56 67.2 67.2 46.2
C5-17 (C5-37) Motor Inertia
kgm
2
0.220 0.273 0.273 0.333 0.333 0.490 0.49 0.90
C6-02 Carrier Frequency Selection – 1 7 1 7 1 7 1 7
E2-01 (E4-01) Motor Rated Current A 52.3 65.6 65.6 79.7 79.7 95 95 130
E2-02 (E4-02) Motor Rated Slip Hz 1.8 1.33 1.33 1.6 1.6 1.46 1.46 1.39
E2-03 (E4-03) Motor No-Load Current A 10.9 19.1 19.1 22 22 24 24 36
No. Name Unit Default Settings
Model CIMR-A – 4A0009 4A0011 4A0018 4A0023
C6-01 Drive Duty Selection –
HD ND HD ND HD ND HD ND
0 1 0 1 0 1 0 1
o2-04 Drive Model Selection Hex. 96 97 99 9A
E2-11 (E4-11) Motor rated Output kW 3.0 3.7 3.7 5.5 5.5 7.5 7.5 11