Doc ID :ADR233B/IM/01
Ref ID : ADR233B/IM/UG
Rev No. : 05
ADR233B
Ground OC
Ground OC
Editable Setting
Password protected window for “Ground OC” setting i.e.
IE>1 Enable, IE>2 Enable and IE>3 Enable can be set as
Disabled / Enabled.
Press the Right arrow key () to move to the next option.
Ground OC
IE>1 Enable
Enabled
Editable Setting
By using the Plus / Up arrow key (+ /) or the Minus / Down
arrow key (- /) the IE>1 Enable can be set i.e. Disabled /
Enabled.
Note : When set as Enabled
Press the Right arrow key () to move to the next option.
Ground OC
IE>1 Curve
IEEE M Inverse
Editable Setting
By using the Plus / Up arrow key (+ /) or the Minus / Down
arrow key (- /) the IE>1 Curve can be set i.e. Definite Time
/ IEC S Inverse / ST Inverse 1.3S / IEC V Inverse / IEC E
Inverse / UK LT Inverse / IEEE M Inverse / IEEE V Inverse /
IEEE E Inverse / US Inverse / US ST Inverse.
Note: When set as IEEE M Inverse
Press the Minus / Down arrow key (- /) to move to the next
option.
Ground OC
IE>1
1.00 A
0.05 – 4.00 xIn
Editable Setting
By using the Plus / Up arrow key (+ /) or the Minus / Down
arrow key (- /) the IE>1 can be set.
The setting range is from 0.05 to 4.00 xIn in step of 0.01 xIn.
Press the Minus / Down arrow key (- /) to move to the next
option.
Ground OC
IE>1 Time Dial
1.00s
Range 0.01 – 100
Editable setting
By using the Plus / Up arrow key (+ /) or the Minus / Down
arrow key (- /) the IE>1 Time Dial can be set.
The setting range is from 0.01 to 100 in step of 0.01
Press the Minus / Down arrow key (- /) to move to the next
option.