ADR233B
Doc ID : ADR233B_IM_01
Ref ID : ADR233B/IM/FC
Rev No. : 05
Page No. : 432 of 479
9.11.5.2 Ground OC ( IEC Curve )
Ground OC
IE>1
1.
00 A
0.05 – 4.00 xIn
3 4
Ground OC
IE>1 TMS
0.01
Range 0.01 – 1.5
3 4
3 4
Ground OC
t IE>1 D/O Delay
0.01 s
Range 0 – 100s
3 4
3 4
3 4
Ground OC
IE>1 D/O Char
DT
Ground OC
IE>1 2H BLK
Enabled
Ground OC
IE>1 UB2H
4.0 A
4.0 – 32.0 xIn
Ground OC
IE>1 2H Thresh
5 %
Range 5 – 70%
3 4
SAVE Settings
DISCARD Settings
4
Press 3 Key
For Save
Press Target Reset
Key For Cancel
Target Reset
3
6 5
REF
Phase OC
Ground OC
4
Residual OC
6
PROTECTION
CLEAR RECORDS
OUTPUT & LED TEST
GROUP 1
4
Ground OC
Ground OC
4
6 5
Ground OC
IE>1 Enable
Enabled
6 5
Ground OC
IE>1 Curve
IEC S Inverse
Note: The Ground OC settings of IE>2 Enable and IE>3 Enable for all IEC Curves is similar to Ground
OC setting of IE>1 Enable.