BRI-SET, ASAI-ADJ, BRI-DAT
Issue 1 May 2002
8-379555-233-143
BRI Set Audits Test (#630)
This is a series of two tests that are classified as audits. The switch sends
messages to the BRI endpoint to perform the following tests:
■ Ringer Audit – This audit insures that both the switch and the endpoint
agree as to the current state of the endpoint’s ringer.
■ Lamps Audit – This audit insures that both the switch and the endpoint
agree as to the current state of the endpoint’s lamps.
■ Call Activity Audit – This audit insures that the state of calls is consistent
between the switch and the endpoint.
This test is not executed for ASAI or Avaya adjunct because adjuncts do not
employ ringers or lamps, or establish calls on the B channels associated with the
BRI interface.
Table 8-159. Test #630 BRI Set Audits
Error
Code
Tes t
Result Description / Recommendation
1113 ABORT The signaling link between the switch and the endpoint is down.
1. Use the test port PCSSpp long command to clear any errors that prevent
establishment of the signaling link.
2. Examine the results of the Signaling Link Status test (#626) that is run as
part of this command. If this test aborts or fails, follow the repair procedure
for Test #626.
3. If the BRI Set Audits test continues to abort, escalate the problem.
1139 ABORT The EPN’s packet bus is out-of-service.
1. Follow the repair procedures for the packet bus.
2. After completing step 1, execute the test port long PCSSpp command,
and review the results of the BRI Port Local LAN Loop Around test (#618)
to verify the repair.
1141 ABORT The PKT-CTRL is out-of-service.
1. Refer to PKT-CTRL (Packet Control Circuit Pack) Maintenance
documentation.
2. If step 1 does not resolve the problem, escalate to the next tier.
Continued on next page