CABINET (Cabinet Sensors)
Issue 1 May 2002
8-387555-233-143
System Technician-Demanded Tests:
Descriptions and Error Codes
Always investigate tests in the order presented in the table below. By clearing
error codes associated with one test, you may also clear errors generated from
later tests in the sequence.
Order of Investigation
Short Test
Sequence
Long Test
Sequence D/ND*
Battery & Battery Charger Query test (#5)
1
1. See ‘‘POWER’’.
XXND
AC Power Query test (#78)
2
2. See‘‘AC-POWER’’.
XXND
OLS Query test (carrier E) (#127)
3
3. See ‘‘CARR-POW (Carrier Power Supply)’’.
XXND
OLS Query test (carrier D) (#127)
3
XXND
OLS Query test (carrier A) (#127)
3
XXND
OLS Query test (carrier B) (#127)
3
XXND
OLS Query test (carrier C) (#127)
3
XXND
Emergency Transfer Query test (#124)
4
4. See ‘‘EMG-XFER (Emergency Transfer)’’.
XXND
Cabinet Temperature Query test (#122) X X ND
External Alarm Lead Query test (#120)
5
5. See ‘‘EXT-DEV ADMIN? Y (External Device Alarm)’’.
XXND
Analog Ring Generator Initial test (#117)
6
6. See ‘‘RING-GEN’’.
XXND
Analog Ring Generator Query test (#118)
6
XXND