Management
Parameter manual b maXX BM3000
Document no.: 5.12001.07 Baumüller Nürnberg GmbH
338
of 820
4.5
12 QUICK STOP ACTIVE SWITCH ON INHIBIT
n Event:
m "Inhibit Voltage" command or
m QUICK STOP response (Z108.13–) is set to "Inhibit Drive Function" (Pulse Inhib-
it, value 0) or
m Quick Stop has ended (speed 0 reached) or
m Pulse enable input = Low
n Action:
m Drive function is inhibited
16 QUICK STOP ACTIVE OPERATION ENABLED
n Event:
– Drive activation by control word:
m "Enable Operation" command
– Drive activation by hardware control inputs:
m Controller Enable input = High (only if Controller Enable (RF) hardware control in-
put is used)
n Condition:
m Quick Stop input = High (only if Quick Stop (QS) hardware control input is used)
and
m Pulse enable input = High and
m QUICK STOP response (Z108.13–) is set to "Remain in Quick Stop" (value 5 to
8)
n Drive activation by control word:
m Controller Enable input = High (only if Controller Enable (RF) hardware control in-
put is used)
n Action:
m Drive function is enabled
13 All states ERROR RESPONSE ACTIVE
n Event:
m Drive error is detected, i.e., an error to which a response should follow has been
triggered
n Action:
m Error-dependent error response is initiated
14 ERROR RESPONSE ACTIVE ERROR
n Event:
m Error response is complete
n Action:
m Drive function is inhibited
m Switch off the operationally ready relay