Error protocol
case of field-orientated
control (DMC)
High load torques may cause error messages due to
overvoltage.
For an asynchronous motor, switch to sensor-less
control according to V/f characteristic (set P30 to
noise in frequency in-
verter
Reduce switching frequency (P400).
Install input filter.
Install output filter.
Connect motor and frequency inverter to PE poten-
tial.
Install mains and motor cables separately from the
control cables.
resonant frequency of
Set blocking frequencies (P447, P448) and hysteresis
(P449) to disable output frequency ranges.
output signal
defective
Set P475 or P492 to "30 - Technology controller".
Set P476 or P494 to the source for the reference
value.
Set P478 to the source for the actual value.
Start signal (P68 or P69) starts the PID controller.
Check connection for actual value signal.
have 0 V instead
of a voltage of
approx. 20 V
Caused by functionality (see chapter 8.3).
If undesired: Deactivate Energy saving function
(P1511) or select an operation mode, that doesn’t