EasyManua.ls Logo

Optek C4101 - Page 175

Default Icon
208 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Software Version C
- 165 -
optek-converter C4101 Version 07.2009_1.2US, 23.07.2009
www.optek.com
4. The REMOTE IN MONITOR menu appears. If the displays do not
correspond to the current levels (wiring at Remote In), a hardware failure has
probably occurred. The input R5 is not applied in this software.
Fig. 181 Menu Remote In Monitor
5. Press [CLEAR] to return to the previous menu.
Note!
Voltages of 19 - 29 VDC are detected as HIGH and voltages of 0 VDC as
LOW.
With R6 (RZ) = HIGH the system reads in the zero point (ZERO) when
HIGH is confirmed by R8 (RV) = HIGH. The zero point is updated as long
as R6 and R8 are in the HIGH state.
With R7 (RH) the system enables or disables HOLD when HIGH is
confirmed by R8 (RV) = HIGH. The system remains in this state which is
selected by R7 when R8 becomes "LOW".
When defining RV, the set states are taken over, i. e. product change,
system zero point and hold can be triggered in the monitor!
REMOTE IN MONITOR
REMOTE IN R1 : LOW
REMOTE IN R2 : LOW
REMOTE IN R3 : LOW
REMOTE IN R4 : LOW
REMOTE IN R5 : LOW
REMOTE IN RZ : LOW
REMOTE IN RH : LOW
REMOTE IN RV : LOW
20:05:2006 P01 11:26:55

Table of Contents