Software Version C
- 65 -
optek-converter C4101 Version 07.2009_1.2US, 23.07.2009
www.optek.com
9.5.3.5 Measuring result - multiplication with slope + offset
With this function, you can additionally multiply the selected measuring function
by one of the eight slope + offset sets (SUF01-SUF08) to evaluate the detector
signals. The tables contain one value for the slope and one value for offset and
have to be defined first. To do this, proceed as described in chapter 9.5.5.2,
page 75.
When "- - -" is selected, the measuring result does not change. Default values
are 1.0000 for the slope and 0.0000 for the offset.
1. Select X SLOPE + OFFSET and press [ENTER].
2. A list with tables appears. Select an option.
Fig. 55 Setting measuring result - multiplication with slope + offset
3. Press [ENTER]. The RANGE BEGIN / END menu item is marked.
4. Save the new setting.
MEASURING RESULT: M01
DEFINE NAME: M01
FUNCTION ---
SUF01
SUF02
SUF03
SUF04
SUF05
SUF06
SUF07
SUF08
X mA INPUT
X LINEARIZATION
X SLOPE + OFFSET
RANGE BEGIN / END
UNIT
FORMAT
REJECT P01 SAVE