Wiring
- 24 -
optek-converter C4101 Version 07.2009_1.2US, 23.07.2009
www.optek.com
Tool Screw driver
To be able to allocate the end splices unequivocally to the clamps of the
converter, each end splice is marked with the number of the correct clamp:
Detector cable to sensor
1 = white (A1) 2 = brown (A2) 5 = black (A5)
Lamp cable to sensor
6 = white or blue (6) 7 = brown (7)
Caution!
Lamp voltage must be adjusted to the cable length in order to compensate
voltage loss in the cable. Too low lamp voltage can lead to wrong measuring
results. Too high lamp voltage reduces the life of the lamp module considerably.