Chapter 13 — Drive Troubleshooting Troubleshooting Drives
November 2016 User Guide—Spectra T950 Library
415
6 (cont.) Confirmthatthecartridgeisthecorrectmediatype.Ifitis,determinewhether
theproblemisassociatedwithwritingorreadingdatatoasinglecartridgeor
multiplecartridges.
ProblemsWritingDataonaCartridgewithaKnownBarcode
Retrytheoperationwithadifferentcartridge.
Iftheoperationsucceeds,theoriginalcartridgewasdefective.Ifpossible,copy
datafromthedefectivecartridgeandsettheoriginalcartridgeaside.Ifadditional
testsconfirmthatthecartridgewasthe sourceoftheerror,youcandiscardit.
Iftheoperationfailsandanotherdriveisavailable,inserttheoriginal
cartridgeintotheotherdriveandretrytheoperation.
Iftheoperationfails,discardthedefectivecartridge.
Iftheoperationsucceeds,usetheDriveHealthVerificationwizardtotest
theoriginaldrive(see
UsingDLMtoTesta Driveonpage427).
IfthedrivefailstheDLMdrivetest,contactSpectraLogicTechnicalSupport
(see
ContactingSpectraLogiconpage7).
IfthedrivepassestheDLMdrivetest,theerrorwastemporary.
Iftheoperationfailsandanotherdriveisnotavailable,usetheDriveHealth
Verificationwizardtotestthedrive.
IfthedrivefailstheDLMdrivetest,contactSpectraLogicTechnicalSupport.
IfthedrivepassestheDLMdrivetest,retrytheoperationtodeterminewhether
theerrorwastemporary.Iftheoperationfailsagain,discardthecartridge.
ProblemsReadingDataonaCartridgewithaKnownBarcode
Performoneofthefollowingprocedures:
Ifanotherdriveisavailable,insertthecartridgeintotheotherdriveandretry
theoperation.
Iftheoperationfails,discardthedefectivecartridge.
Iftheoperationsucceeds,usetheDriveHealthVerificationwizardtotest
theoriginaldrive(see
UsingDLMtoTesta Driveonpage427).
IfthedrivefailstheDLMdrivetest,contactSpectraLogicTechnicalSupport
(see
ContactingSpectraLogiconpage7).
Ifthediagnosticssucceed,theerrorwastemporary.
Ifanotherdriveisnotavailable,usetheDriveHealthVerificationwizardto
testthedrive.
IfthedrivefailstheDLMdrivetest,contactSpectraLogicTechnicalSupport.
IfthedrivepassestheDLMdrivetest,retrytheoperationtodeterminewhether
theerrorwastemporary.Iftheoperationfailsagain,discardthecartridge.
ProblemswithOneorMoreCartridgeswithUnknownBarcodes
Iftheproblemoccurswithmultipletapecartridgesorifyoudonotknowthe
tapecartridge’sbarcode,usetheDriveHealthVerificationwizardtotestthe
drive(seeUsingDLMtoTestaDriveonpage427).
IfthedrivefailstheDLMdrivetest,contactSpectraLogicTechnicalSupport
(see
ContactingSpectraLogiconpage7).
IfthedrivepassestheDLMdrivetest,theproblemisnotrelatedtothedrive.
Code DLM
Health
Icon
Cause and Solution