6.3 Drive Alarms, Faults, and Errors
332 YASKAWA ELECTRIC SIEP C710616 27G YASKAWA AC Drive A1000 Technical Manual
Table 6.10 Fault Displays (2)
Digital Operator Display
Name Page
Digital Operator Display
Name Page
LED Operator LCD Operator LED Operator LCD Operator
oFb01 Option Card Fault at Option Port CN5-B 343 oPr External Digital Operator Connection Fault 346
oFb02 Option Card Fault at Option Port CN5-B 343 oS Overspeed 346
,
oFb03, oFb11
Option Card Error Occurred at Option Port
C
N5-B
343
ov Overvoltage 346
PF Input Phase Loss 347
to
oFb12 to oFb17
Option Card Error Occurred at Option Port
C
N5-B
343
PGo PG Disconnect (for Control Mode with PG) 347
PGoH PG Hardware Fault (when using PG-X3) 347
<4>
oFC00
Option Card Connection Error at Option
Po
rt CN5-C
343 rF Braking Resistor Fault 347
oFC01 Option Card Fault at Option Port CN5-C 343 rH Braking Resistor Overheat 347
oFC02 Option Card Fault at Option Port CN5-C 344 rr Dynamic Braking Transistor 347
,
<1> Displayed as or when occurring at drive power up. When one of the faults occurs after successfully starting the drive, the
display will show or .
<2> Occurs in models CIMR-A4A0930 and 4A1200.
<3> This function prevents continuous operation in reverse when using high frequency injection (n8-57 = 1) in the Advanced Open Loop Vector
Control mode for PM motors (A1-02 = 6) with a motor for which no motor code has been entered (it does not simply prevent reverse
operation). To quickly detect undesirable reverse operation, set L8-93, L8-94, and L8-95 to low values within range of erroneous detection.
<4> Fault trace (i.e., the fault history) is not kept when CPF00, CPF01, CPF06, CPF24, oFA00, oFb00, oFC00, Uv1, Uv2, and Uv3 occur.
oFC03, oFC11
Option Card Error Occurred at Option Port
C
N5-C
344
SC Output Short-Circuit or IGBT Fault 348
SEr Too Many Speed Search Restarts 348
to
oFC12 to oFC17
Option Card Error Occurred at Option Port
C
N5-C
344 STo Pull-Out Detection 348
to
oFC50 to oFC55
Option Card Error Occurred at Option Port
C
N5-C
344 SvE Zero Servo Fault 348
oH Heatsink Overheat 344
<2>
THo Thermistor Disconnect 348
oH1 Overheat 1 (Heatsink Overheat) 344 UL3 Undertorque Detection 1 348
oH3 Motor Overheat Alarm (PTC Input) 344 UL4 Undertorque Detection 2 348
oH4 Motor Overheat Fault (PTC Input) 344 UL5 Mechanical Weakening Detection 2 348
<2>
oH5 Motor Overheat (NTC Input) 345
<2>
UnbC Current Unbalance 349
oL1 Motor Overload 345
<4>
Uv1 DC Bus Undervoltage 349
oL2 Drive Overload 345
<4>
Uv2 Control Power Supply Voltage Fault 349
oL3 Overtorque Detection 1 345
<4>
Uv3
Undervoltage 3 (Soft-Charge Bypass
C
ircuit Fault)
349
oL4 Overtorque Detection 2 345
<2>
Uv4 Gate Drive Board Undervoltage 349
oL5 Mechanical Weakening Detection 1 345 voF Output Voltage Detection Fault 349
oL7 High Slip Braking oL 346 – – – –