Startup Procedure and
Test Run
3
3.6 Keypad Operation
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual 161
4. Push or to select [Analog Gauge], then push (Setup).
5. Push .
6. Push or to select the monitor number to register, then push .
Enter the three digits in “x-xx” part of monitor Ux-xx to identify which monitor to output. For example, to
show monitor U1-01 [Frequency Reference], set it to "101" as shown in this figure.
The configuration procedure is complete.
◆ Display Monitors as an Analog Gauge
The following explains how to display the contents selected for a monitor as an analog gauge.
1. Push (Home) to show the HOME screen.
Note:
• The keypad will show [Home] in the top right corner when the HOME screen is active.
• If [Home] is not on , push (Back) to show [Home] on .
2. Push (Menu).
3. Push or to select [Monitors], then push .