Startup Procedure and
Test Run
3
3.8 Auto-Tuning
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual 193
■ Input Data for Induction Motor Auto-Tuning
To do Auto-Tuning, input data for the items in Table 3.7 that have an "x". Before starting Auto-Tuning, record the
information on the motor nameplate as a reference.
Table 3.7 Input Data for Induction Motor Auto-Tuning
Input Data Parameters Unit
Auto-Tuning Mode
(T1-01 Value)
Rotational Auto-
Tuning
(0)
Stationary Auto-
Tuning 1
(1)
Stationary Line-
Line Resistance
(2)
Motor Rated Power T1-02 kW x x x
Motor Rated Voltage T1-03 V x x -
Motor Rated Current T1-04 A x x x
Motor Base
Frequency
T1-05 Hz x x -
Number of Poles T1-06 - x x -
Motor Base Speed T1-07 min
-1
x x -
Encoder Pulse Count
(PPR)
T1-08 - x
*1
x
*1
-
Motor No-Load
Current
T1-09 A - x -
Motor Rated Slip
Frequency
T1-10 Hz - x
*2
-
Motor Iron Loss T1-11 W x
*3
- -
Test Mode Selection
*4
T1-12 - - x
*5
-
No-Load Voltage T1-13 V x
*6
x
*6
-
*1 Input this value when A1-02 = 3 [Control Method Selection = Closed Loop Vector].
*2 0 Hz is displayed as the initial value. If you do not know the Motor Rated Slip Frequency, keep the setting at 0 Hz.
*3 Input this value when A1-02 = 0 or 1 [Control Method Selection = V/f Control or V/f Control with Encoder].
*4 If T1-12 = 1 [Test Mode Selection = Yes], when you run the motor in Drive Mode for the first time after Auto-Tuning, the drive will
automatically set E2-02 [Motor Rated Slip] and E2-03 [Motor No-Load Current].
*5 Input this value when T1-10 [Motor Rated Slip Frequency] = 0 Hz.
*6 Set the same value to No-Load Voltage as T1-03 [Motor Rated Voltage] to get the same characteristics using Yaskawa 1000-Series
drives or other legacy models.
◆ Auto-Tuning for PM Motors
This section gives information about Auto-Tuning for PM motors. Set these parameters for Auto-Tuning:
• Motor parameters E1-xx, E5-xx
• Speed feedback detection uses F1-xx (only with CLV/PM)