H4: Analog Outputs
H4 parameters set the drive analog monitors. These parameters select monitor parameters, adjust gain and bias,
and select output signal levels.
Calibrate Meters Connected to MFAO Terminals FM and AM
You can use H4-02, H4-03, H4-05, and H4-06 [FM/AM Analog Output Gain/Bias] to calibrate meters connected
to terminals FM and AM.
No. Name Setting Range Default Setting
H4-02 Terminal FM Analog Output Gain -999.9 - 999.9% 100.0%
H4-03 Terminal FM Analog Output Bias -999.9 - 999.9% 0.0%
H4-05 Terminal AM Analog Output Gain -999.9 - 999.9% 50.0%
H4-06 Terminal AM Analog Output Bias -999.9 - 999.9% 0.0%
H4-07 Terminal FM Signal Level Select
0: 0-10 VDC
1: -10 +10 VDC
2: 4-20 mA
0
H4-08 Terminal AM Signal Level Select
0: 0-10 VDC
1: -10 +10 VDC
2: 4-20 mA
0
Figure 11.114 shows the gain and bias.
Figure 11.114 Analog Output Gain/Bias Configuration Example 1
For example, when the parameter value set to analog output is 0, and a 3 V signal is output to terminal FM, H4-03
[FM Analog Output Bias] is set to 30%.
Figure 11.115 Analog Output Gain/Bias Configuration Example 2
Calibrate Terminal FM
Stop the drive to calibrate meters. Use this procedure to calibrate:
1. Show H4-02 [FM Analog Output Gain] on the keypad.