Parameter List
10
10.8 E: Motor Parameters
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual 525
10.8 E: Motor Parameters
◆ E1: V/f Pattern for Motor 1
No.
(Hex.)
Name Description
Default
(Range)
Ref.
E1-01
(0300)
Input AC Supply
Voltage
Sets the drive input voltage.
NOTICE: Set this parameter to align with the drive input
voltage (not motor voltage). The protective features of the
drive will not function if this parameter is incorrect. Failure to
obey will cause incorrect drive operation.
200 V Class: 230
V, 400 V: 400 V
(200 V Class: 155
to 255 V, 400 V
Class: 310 to 510
V)
799
E1-03
(0302)
V/f Pattern
Selection
Sets the V/f pattern for the drive and motor. You can use one of the
preset patterns or you can make a custom pattern.
0 : Const Trq, 50Hz base, 50Hz max
1 : Const Trq, 60Hz base, 60Hz max
2 : Const Trq, 50Hz base, 60Hz max
3 : Const Trq, 60Hz base, 72Hz max
4 : VT, 50Hz, 65% Vmid reduction
5 : VT, 50Hz, 50% Vmid reduction
6 : VT, 60Hz, 65% Vmid reduction
7 : VT, 60Hz, 50% Vmid reduction
8 : High Trq, 50Hz, 25% Vmin boost
9 : High Trq, 50Hz, 65% Vmin boost
A : High Trq, 60Hz, 25% Vmin boost
B : High Trq, 60Hz, 65% Vmin boost
C : High Freq, 60Hz base, 90Hz max
D : High Freq, 60Hz base, 120Hz max
E : High Freq, 60Hz base, 180Hz max
F : Custom
Note:
• When A1-02 = 2 [Control Method Selection = Open Loop
Vector], settings 0 through E are not available.
• Set the correct V/f pattern for the application and operation
area. An incorrect V/f pattern can decrease motor torque and
increase current from overexcitation.
F
(Determined by
A1-02)
799
E1-04
(0303)
Maximum Output
Frequency
Sets the maximum output frequency for the V/f pattern.
Determined by A1-
02 and E5-01
(Determined by
A1-02 and E5-01)
804
E1-05
(0304)
Maximum Output
Voltage
Sets the maximum output voltage for the V/f pattern.
Determined by A1-
02
(200 V Class: 0.0 -
255.0 V, 400 V
Class: 0.0 - 510.0
V)
805
E1-06
(0305)
Base Frequency
Sets the base frequency for the V/f pattern.
Determined by A1-
02 and E5-01
(0.0 - E1-04)
805
E1-07
(0306)
Mid Point A
Frequency
Sets a middle output frequency for the V/f pattern.
Determined by A1-
02
(0.0 - E1-04)
805
E1-08
(0307)
Mid Point A
Voltage
Sets a middle output voltage for the V/f pattern.
Determined by A1-
02,C6-01 and o2-
04
(200 V Class: 0.0
to 255.0 V,
400 V Class: 0.0 to
510.0 V)
805