10.22 Parameters Changed by PM Motor Code Selection
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual 647
10.22 Parameters Changed by PM Motor Code Selection
Note:
The motor codes listed in these tables are the only correct setting values.
◆ Yaskawa SMRA Series SPM Motors
Table 10.4 SMRA Series Motor Code Setting for Specification of 200 V at 1800 min
-1
(r/min)
No. Name Unit Motor Code (setting value of E5-01)
E5-01
PM Motor Code
Selection
- 0002 0003 0005 0006 0008
Voltage Class V 200 200 200 200 200
Capacity kW 0.4 0.75 1.5 2.2 3.7
Motor Rotation Speed min
-1
1800 1800 1800 1800 1800
E5-02
PM Motor Rated
Power (kW)
kW 0.4 0.75 1.5 2.2 3.7
E5-03
PM Motor Rated
Current (FLA)
A 2.1 4.0 6.9 10.8 17.4
E5-04 PM Motor Pole Count - 8 8 8 8 8
E5-05
PM Motor Resistance
(ohms/phase)
Ω 2.47 1.02 0.679 0.291 0.169
E5-06
PM d-axis Inductance
(mH/phase)
mH 12.7 4.8 3.9 3.6 2.5
E5-07
PM q-axis Inductance
(mH/phase)
mH 12.7 4.8 3.9 3.6 2.5
E5-09
PM Back-EMF Vpeak
(mV/(rad/s))
mVs/rad 0 0 0 0 0
E5-24
PM Motor Induced
Voltage Constant 2
(Ke)
mV/(r/min) 62.0 64.1 73.4 69.6 72.2
E1-04
Maximum Output
Frequency
Hz 120 120 120 120 120
E1-05
Maximum Output
Voltage
V 200.0 200.0 200.0 200.0 200.0
E1-06 Base Frequency Hz 120 120 120 120 120
E1-09
Minimum Output
Frequency
Hz 6 6 6 6 6
C5-17 Motor Inertia kgm
2
0.0007 0.0014 0.0021 0.0032 0.0046
L3-24
Motor Accel Time for
Inertia Cal
s 0.064 0.066 0.049 0.051 0.044
n5-02
Motor Acceleration
Time
s 0.064 0.066 0.049 0.051 0.044
n8-49
d-Axis Cur
forHighEfficiency
Cont
% 0 0 0 0 0
Table 10.5 SMRA Series Motor Code Setting for Specification of 200 V at 3600 min
-1
(r/min)
No. Name Unit Motor Code (setting value of E5-01)
E5-01
PM Motor Code
Selection
- 0103 0105 0106 0108
Voltage Class V 200 200 200 200
Capacity kW 0.75 1.5 2.2 3.7
Motor Rotation Speed min
-1
3600 3600 3600 3600
E5-02
PM Motor Rated
Power (kW)
kW 0.75 1.5 2.2 3.7