Parameter List
10
10.6 C: Tuning
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual 513
10.6 C: Tuning
◆ C1: Accel & Decel Time
No.
(Hex.)
Name Description
Default
(Range)
Ref.
C1-01
(0200)
RUN
Acceleration Time
1
Sets the length of time to accelerate from zero to maximum output
frequency.
10.0 s
(0.0 - 6000.0 s)
751
C1-02
(0201)
RUN
Deceleration Time
1
Sets the length of time to decelerate from maximum output
frequency to zero.
10.0 s
(0.0 - 6000.0 s)
751
C1-03
(0202)
RUN
Acceleration Time
2
Sets the length of time to accelerate from zero to maximum output
frequency.
10.0 s
(0.0 - 6000.0 s)
751
C1-04
(0203)
RUN
Deceleration Time
2
Sets the length of time to decelerate from maximum output
frequency to zero.
10.0 s
(0.0 - 6000.0 s)
751
C1-05
(0204)
RUN
Acceleration Time
3
Sets the length of time to accelerate from zero to maximum output
frequency.
10.0 s
(0.0 - 6000.0 s)
751
C1-06
(0205)
RUN
Deceleration Time
3
Sets the length of time to decelerate from maximum output
frequency to zero.
10.0 s
(0.0 - 6000.0 s)
751
C1-07
(0206)
RUN
Acceleration Time
4
Sets the length of time to accelerate from zero to maximum output
frequency.
10.0 s
(0.0 - 6000.0 s)
752
C1-08
(0207)
RUN
Deceleration Time
4
Sets the length of time to decelerate from maximum output
frequency to zero.
10.0 s
(0.0 - 6000.0 s)
752
C1-09
(0208)
Fast Stop Time
Sets the length of time that the drive will decelerate to zero for a
Fast Stop.
Note:
• Decelerating too quickly can cause an ov [Overvoltage] fault
that shuts off the drive while the motor to coasts to a stop. Set a
Fast Stop time in C1-09 that prevents motor coasting and makes
sure that the motor stops quickly and safely.
• When L2-29 = 0 [Kinetic Energy Backup Method = Single
Drive KEB Ride-Thru 1] and you do KEB Auto-Tuning, the
drive will automatically set C1-09. If you must not change the
Fast Stop time, do not do KEB Auto-Tuning.
10.0 s
(0.0 - 6000.0 s)
752
C1-10
(0209)
Accel/Decel Time
Setting Units
Sets the setting units for C1-01 to C1-08 [Accel/Decel Times 1 to 4],
C1-09 [Fast Stop Time], L2-06 [Kinetic Energy Backup Decel
Time], and L2-07 [Kinetic Energy Backup Accel Time].
0 : 0.01 s (0.00 to 600.00 s)
1 : 0.1 s (0.0 to 6000.0 s)
1
(0, 1)
752
C1-11
(020A)
Accel/Decel Time
Switchover Freq
Sets the frequency at which the drive will automatically change
acceleration and deceleration times.
Determined by A1-
02
(0.0 - 590.0 Hz)
753
C1-14
(0264)
Accel/Decel Rate
Frequency
Sets the base frequency used to calculate acceleration and
deceleration rates.
0.0 Hz
(0.0 - 590.0 Hz)
753