EasyManua.ls Logo

YASKAWA GA700 - 10.21 Defaults by Drive Model and Duty Rating ND;HD; Class

YASKAWA GA700
1053 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter List
10
10.21 Defaults by Drive Model and Duty Rating ND/HD
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual 623
10.21 Defaults by Drive Model and Duty Rating ND/HD
The values for the parameters in these tables depend on the values for parameters o2-04 and C6-01. Changing the
settings for o2-04 and C6-01 will change the default settings.
200 V class
No.
*1
Name Unit Default
- Drive Model - 2004 2006 2010
C6-01
Normal /
Heavy Duty
Selection
-
HD (ND) HD (ND) HD (ND)
0 1 0 1 0 1
o2-04
Drive Model
(KVA)
Selection
Hex. 62 63 65
E2-11
(E4-11)
Motor
Rated
Power (kW)
kW 0.55 0.75 0.75 1.1 1.5 2.2
b3-04
V/f Gain
during Speed
Search
% 100 100 100 100 100 100
b3-06
Speed
Estimation
Current Level
1
- 1 1 0.5 0.5 0.5 0.5
b3-08
Speed
Estimation
ACR P Gain
- 0.5 0.5 0.5 0.5 0.5 0.5
b3-26
Direction
Determina
tion Level
- 1000 1000 1000 1000 1000 1000
b8-03
Energy
Saving Filter
Time
s 0.50 0.50 0.50 0.50 0.50 0.50
b8-04
Energy
Saving
Coefficient
Value
- 288.2 223.7 223.7 196.6 169.4 156.8
C5-17
(C5-37)
Motor Inertia kgm
2
0.0015 0.0028 0.0028 0.0068 0.0068 0.0088
C6-02
Carrier
Frequency
Selection
- 1 7 1 7 1 7
E2-01
(E4-01)
Motor Rated
Current
(FLA)
A 1.9 3.3 3.3 4.9 6.2 8.5
E2-02
(E4-02)
Motor Rated
Slip
Hz 2.9 2.5 2.5 2.6 2.6 2.9
E2-03
(E4-03)
Motor No-
Load Current
A 1.2 1.8 1.8 2.3 2.8 3
E2-05
(E4-05)
Motor Line-
to-Line
Resistance
Ω 9.842 5.156 5.156 3.577 1.997 1.601
E2-06
(E4-06)
Motor
Leakage
Inductance
% 18.2 13.8 13.8 18.5 18.5 18.4
E2-10
(E4-10)
Motor Iron
Loss
W 14 26 26 38 53 77
E5-01
PM Motor
Code
Selection
- 1202 1202 1203 1203 1205 1205