10.21 Defaults by Drive Model and Duty Rating ND/HD
624 YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
No.
*1
Name Unit Default
- Drive Model - 2004 2006 2010
C6-01
Normal /
Heavy Duty
Selection
-
HD (ND) HD (ND) HD (ND)
0 1 0 1 0 1
o2-04
Drive Model
(KVA)
Selection
Hex. 62 63 65
E2-11
(E4-11)
Motor
Rated
Power (kW)
kW 0.55 0.75 0.75 1.1 1.5 2.2
L2-02
Power Loss
Ride Through
Time
s 0.1 0.1 0.2 0.2 0.3 0.3
L2-03
Minimum
Baseblock
Time
s 0.2 0.3 0.3 0.4 0.4 0.5
L2-04
Powerloss V/f
Recovery
Ramp Time
s 0.3 0.3 0.3 0.3 0.3 0.3
L2-05
Undervoltage
Detection Lvl
(Uv1)
- 190 190 190 190 190 190
L3-24
Motor Accel
Time @
Rated Torque
s 0.178 0.142 0.142 0.142 0.166 0.145
L8-02
Overheat
Alarm Level
°C 115 115 115 115 115 115
L8-09
Output
Ground Fault
Detection
- 1 1 1 1 1 1
L8-38
Carrier
Frequency
Reduction
- 2 2 2 2 2 2
n1-01
Hunting
Prevention
Selection
- 1 1 1 1 1 1
n1-03
Hunting
Prevention
Time
Constant
ms 10 10 10 10 10 10
n1-16
Hunting
Prevention
High Fc Gain
- 0.50 0.50 0.50 0.50 0.50 0.50
n5-02
Motor Inertia
Acceleration
Time
s 0.178 0.142 0.142 0.142 0.166 0.145
n8-11
Observer
Calculation
Gain 2
- 30.0 30.0 30.0 30.0 30.0 30.0
*1 Parameters within parentheses are for motor 2.