2.15 Control I/O Connections
114 YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
◆ Set Sinking Mode/Sourcing Mode
Close the circuit between terminals SC-SP and SC-SN to set the sinking mode/sourcing mode and the internal/
external power supply for the MFDI terminals. The default setting for the drive is internal power supply sinking
mode.
NOTICE: Do not close the circuit between terminals SP and SN. Failure to obey will cause damage to the drive.
Mode Internal Power Supply (Terminal SN-SP) External Power 24 V
Sinking Mode
(NPN)
Sourcing Mode
(PNP)
◆ Set Input Signals for MFAI Terminals A1 to A3
Use terminals A1 to A3 to input a voltage or a current signal. Set the signal type as shown in Table 2.28.
Figure 2.114 Location of DIP Switch S1
Table 2.28 MFAI Terminals A1 to A3 Signal Settings
Termi
nal
Input
Signal
DIP Switch Settings Parameters
Switch Setting No. Signal Level
A1
Voltage
input
S1-1
V
(Default)
H3-01
0: 0 V to 10 V/0% to 100% (input impedance: 20 kΩ)
1: -10 V to +10 V/-100% to 100%
Current
input
I
2: 4 mA to 20 mA/0% to 100%
3: 0 mA to 20 mA/0% to 100% (input impedance: 250 Ω)
A2
Voltage
input
S1-2
V
H3-09
0: 0 V to 10 V/0% to 100% (input impedance: 20 kΩ)
1: -10 V to +10 V/-100% to 100%
Current
input
I
(Defaul)
2: 4 mA to 20 mA/0% to 100%
3: 0 mA to 20 mA/0% to 100% (input impedance: 250 Ω)