11.8 H: Terminal Functions
886 YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
7E: Reverse Rotation Identifier
Setting Function Description
7E Reverse Rotation
Identifier
Sets the rotation direction of the motor when in Simple Closed Loop V/f Control method and F1-
21, F1-37 = 0 [Encoder Option Function Selection = A pulse detection], or when in Closed Loop
V/f Control method.
ON : Reverse
Detects if the motor is rotating in the reverse direction.
OFF : Forward
Detects if the motor is rotating in the forward direction.
7F: PID Bi-Directional Enable
Setting Function Description
7F PID Bi-Directional
Enable
Sets operation of the PID Bi-Directional function.
ON : Enabled
OFF : Disabled
90 to 97: DriveWorksEZ Digital Inputs 1 to 8
Setting Function Description
90 to 97 DriveWorksEZ
Digital Inputs 1 to 8
Sets digital inputs used with DriveWorksEZ. Refer to the DriveWorksEZ Online Manual for more
information.
Note:
You cannot set values 90 to 97 for inverse output.
9F: DWEZ Disable
Setting Function Description
9F DWEZ Disable
Sets operation of the DriveWorksEZ program saved in the drive.
Note:
Set A1-07 = 2 [DriveWorksEZ Function Selection = Digital input] to use this function.
ON : Disabled
OFF : Enabled
101 to 19F: Inverse Input of 1 to 9F
Setting Value Function Description
101 to 19F Inverse Input of 1 to 9F Sets the function of the selected MFDI to operate inversely. To select the function, enter
1xx, where the xx is the function setting value.
For example, to use the inverse input of E [ASR Integral Reset], set H1-xx = 10E.
Note:
You cannot use inverse input for all functions. Refer to Table 11.59 for more information.
H2: Multi-function Digital Output
H2 parameters set the MFDO terminal functions.
H2-01 to H2-03 Terminal M1-M2, M3-M4, M5-M6 Function Selection
The drive has three MFDO terminals. Table 11.64 shows the default function settings for the terminals.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV