10.9 F: Options
536 YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
◆ F5: Digital Output Option
No.
(Hex.)
Name Description
Default
(Range)
Ref.
F5-01
(0399)
Terminal P1-PC
Function Select
Sets the function of terminal P1-PC on the DO-A3 option. Set F5-09
= 2 [DO-A3 Output Mode Selection = Programmable (F5-01 to F5-
08)] to enable this function.
0
(0 - 1A7)
838
F5-02
(039A)
Terminal P2-PC
Function Select
Sets the function of terminal P2-PC on the DO-A3 option. Set F5-09
= 2 [DO-A3 Output Mode Selection = Programmable (F5-01 to F5-
08)] to enable this function.
1
(0 - 1A7)
838
F5-03
(039B)
Terminal P3-PC
Function Select
Sets the function of terminal P3-PC on the DO-A3 option. Set F5-09
= 2 [DO-A3 Output Mode Selection = Programmable (F5-01 to F5-
08)] to enable this function.
2
(0 - 1A7)
838
F5-04
(039C)
Terminal P4-PC
Function Select
Sets the function of terminal P4-PC on the DO-A3 option. Set F5-09
= 2 [DO-A3 Output Mode Selection = Programmable (F5-01 to F5-
08)] to enable this function.
4
(0 - 1A7)
838
F5-05
(039D)
Terminal P5-PC
Function Select
Sets the function of terminal P5-PC on the DO-A3 option. Set F5-09
= 2 [DO-A3 Output Mode Selection = Programmable (F5-01 to F5-
08)] to enable this function.
6
(0 - 1A7)
839
F5-06
(039E)
Terminal P6-PC
Function Select
Sets the function of terminal P6-PC on the DO-A3 option. Set F5-09
= 2 [DO-A3 Output Mode Selection = Programmable (F5-01 to F5-
08)] to enable this function.
37
(0 - 1A7)
839
F5-07
(039F)
Terminal M1-M2
Function Select
Sets the function of terminal M3-M2 on the DO-A3 option. Set F5-
09 = 2 [DO-A3 Output Mode Selection = Programmable (F5-01 to
F5-08)] to enable this function.
F
(0 - 1A7)
839
F5-08
(03A0)
Terminal M3-M4
Function Select
Sets the function of terminal M3-M4 on the DO-A3 option. Set F5-
09 = 2 [DO-A3 Output Mode Selection = Programmable (F5-01 to
F5-08)] to enable this function.
F
(0 - 1A7)
839
F5-09
(03A1)
DO-A3 Output
Mode Selection
Sets the output mode of signals from the DO-A3 option.
0 : Predefined Individual Outputs
1 : Binary Output
2 : Programmable (F5-01 to F5-08)
0
(0 - 2)
839
◆ F6: Communication Options
No.
(Hex.)
Name Description
Default
(Range)
Ref.
F6-01
(03A2)
Communication
Error Selection
Sets the method to stop the motor or let the motor continue
operating when the drive detects a bUS [Option Communication
Error].
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
3 : Alarm Only
4 : Alarm (Run at d1-04)
5 : Alarm - Ramp Stop
1
(0 - 5)
841
F6-02
(03A3)
Comm External
Fault (EF0) Detect
Sets when the drive will detect EF0 [Option Card External Fault] is
detected.
0 : Always Detected
1 : Detected during RUN Only
0
(0, 1)
841