Parameter List
10
10.9 F: Options
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual 537
No.
(Hex.)
Name Description
Default
(Range)
Ref.
F6-03
(03A4)
Comm External
Fault (EF0) Select
Sets the method to stop the motor or let the motor continue
operating when the drive detects an EF0 [Option Card External
Fault].
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
3 : Alarm Only
1
(0 - 3)
841
F6-04
(03A5)
bUS Error
Detection Time
Sets the delay time for the drive to detect bUS [Option
Communication Error].
Note:
When you install an option card in the drive, the parameter value
changes to 0.0 s.
2.0 s
(0.0 - 5.0 s)
842
F6-06
(03A7)
Torque Reference/
Limit by Comm
Sets the function that enables and disables the torque reference and
torque limit received from the communication option.
0 : Disabled
1 : Enabled
0
(0, 1)
842
F6-07
(03A8)
Multi-Step Ref @
NetRef/ComRef
Sets the function that enables and disables the multi-step speed
reference when the freqency reference source is NetRef or ComRef
(communication option card or MEMOBUS/Modbus
communications).
0 : Disable Multi-Step References
1 : Enable Multi-Step References
0
(0, 1)
842
F6-08
(036A)
Comm Parameter
Reset @Initialize
Sets the function to initialize F6-xx and F7-xx parameters when the
drive is initialized with A1-03 [Initialize Parameters].
0 : No Reset - Parameters Retained
1 : Reset Back to Factory Default
0
(0, 1)
842
F6-10
(03B6)
CC-Link Node
Address
Sets the node address for CC-Link communication. Restart the drive
after changing this setting.
Note:
Be sure to set a node address that is different than all other node
addresses. Do not set this parameter to 0. Incorrect parameter
settings will cause AEr [Station Address Setting Error] errors
and the L.ERR LED on the option will come on.
0
(0 - 64)
843
F6-11
(03B7)
CC-Link
Communication
Speed
Sets the communication speed for CC-Link communication. Restart
the drive after you change this setting.
0 : 156 kbps
1 : 625 kbps
2 : 2.5 Mbps
3 : 5 Mbps
4 : 10 Mbps
0
(0 - 4)
843
F6-14
(03BB)
BUS Error Auto
Reset
Sets the automatic reset function for bUS [Option Communication
Errors].
0 : Disabled
1 : Enabled
0
(0, 1)
843
F6-16
(0B8A)
Gateway Mode
Sets the gateway mode operation and the number of connected slave
drives.
0 : Disabled
1 : Enabled: 1 Slave Drive
2 : Enabled: 2 Slave Drives
3 : Enabled: 3 Slave Drives
4 : Enabled: 4 Slave Drives
0
(0 - 4)
843