Parameter Details
11
11.5 d: References
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual 781
d1-14: Reference 14
No.
(Hex.)
Name Description
Default
(Range)
d1-14
(028F)
RUN
Reference 14
Sets the frequency reference in the units from o1-03 [Frequency Display
Unit Selection].
0.00 Hz
(0.00 - 590.00 Hz)
Note:
The upper limit value changes when the E1-04 [Maximum Output Frequency] and d2-01 [Frequency Reference Upper Limit] values
change.
When A1-02 = 6, 7 [Control Method Selection = PM Advanced Open Loop Vector, PM Closed Loop Vector], the drive changes o1-03
= 1 [0.01% (100% = E1-04)].
This parameter sets the frequency reference of Multi-Step Speed 14.
d1-15: Reference 15
No.
(Hex.)
Name Description
Default
(Range)
d1-15
(0290)
RUN
Reference 15
Sets the frequency reference in the units from o1-03 [Frequency Display
Unit Selection].
0.00 Hz
(0.00 - 590.00 Hz)
Note:
The upper limit value changes when the E1-04 [Maximum Output Frequency] and d2-01 [Frequency Reference Upper Limit] values
change.
When A1-02 = 6, 7 [Control Method Selection = PM Advanced Open Loop Vector, PM Closed Loop Vector], the drive changes o1-03
= 1 [0.01% (100% = E1-04)].
This parameter sets the frequency reference of Multi-Step Speed 15.
d1-16: Reference 16
No.
(Hex.)
Name Description
Default
(Range)
d1-16
(0291)
RUN
Reference 16
Sets the frequency reference in the units from o1-03 [Frequency Display
Unit Selection].
0.00 Hz
(0.00 - 590.00 Hz)
Note:
The upper limit value changes when the E1-04 [Maximum Output Frequency] and d2-01 [Frequency Reference Upper Limit] values
change.
When A1-02 = 6, 7 [Control Method Selection = PM Advanced Open Loop Vector, PM Closed Loop Vector], the drive changes o1-03
= 1 [0.01% (100% = E1-04)].
This parameter sets the frequency reference of Multi-Step Speed 16.
d1-17: Jog Reference
No.
(Hex.)
Name Description
Default
(Range)
d1-17
(0292)
RUN
Jog Reference
Sets the JOG frequency reference in the units from o1-03 [Frequency
Display Unit Selection]. Set H1-xx = 6 [MFDI Function Select = Jog
Reference Selection] to use the Jog frequency reference.
6.00 Hz
(0.00 - 590.00 Hz)
Note:
The upper limit value changes when the E1-04 [Maximum Output Frequency] and d2-01 [Frequency Reference Upper Limit] values
change.
When A1-02 = 6, 7 [Control Method Selection = PM Advanced Open Loop Vector, PM Closed Loop Vector], the drive changes o1-03
= 1 [0.01% (100% = E1-04)].
d2: Reference Limits
d2 parameters set the upper and lower frequency limits to control the motor speed. Apply these parameters to for
example, run the motor at low-speed due to mechanical strength concerns, or if the motor should not be run at low
speed because of lubrication issues with the gears and bearings.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV