11.5 d: References
780 YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
■ d1-10: Reference 10
No.
(Hex.)
Name Description
Default
(Range)
d1-10
(028B)
RUN
Reference 10
Sets the frequency reference in the units from o1-03 [Frequency Display
Unit Selection].
0.00 Hz
(0.00 - 590.00 Hz)
Note:
• The upper limit value changes when the E1-04 [Maximum Output Frequency] and d2-01 [Frequency Reference Upper Limit] values
change.
• When A1-02 = 6, 7 [Control Method Selection = PM Advanced Open Loop Vector, PM Closed Loop Vector], the drive changes o1-03
= 1 [0.01% (100% = E1-04)].
• This parameter sets the frequency reference of Multi-Step Speed 10.
■ d1-11: Reference 11
No.
(Hex.)
Name Description
Default
(Range)
d1-11
(028C)
RUN
Reference 11
Sets the frequency reference in the units from o1-03 [Frequency Display
Unit Selection].
0.00 Hz
(0.00 - 590.00 Hz)
Note:
• The upper limit value changes when the E1-04 [Maximum Output Frequency] and d2-01 [Frequency Reference Upper Limit] values
change.
• When A1-02 = 6, 7 [Control Method Selection = PM Advanced Open Loop Vector, PM Closed Loop Vector], the drive changes o1-03
= 1 [0.01% (100% = E1-04)].
• This parameter sets the frequency reference of Multi-Step Speed 11.
■ d1-12: Reference 12
No.
(Hex.)
Name Description
Default
(Range)
d1-12
(028D)
RUN
Reference 12
Sets the frequency reference in the units from o1-03 [Frequency Display
Unit Selection].
0.00 Hz
(0.00 - 590.00 Hz)
Note:
• The upper limit value changes when the E1-04 [Maximum Output Frequency] and d2-01 [Frequency Reference Upper Limit] values
change.
• When A1-02 = 6, 7 [Control Method Selection = PM Advanced Open Loop Vector, PM Closed Loop Vector], the drive changes o1-03
= 1 [0.01% (100% = E1-04)].
• This parameter sets the frequency reference of Multi-Step Speed 12.
■ d1-13: Reference 13
No.
(Hex.)
Name Description
Default
(Range)
d1-13
(028E)
RUN
Reference 13
Sets the frequency reference in the units from o1-03 [Frequency Display
Unit Selection].
0.00 Hz
(0.00 - 590.00 Hz)
Note:
• The upper limit value changes when the E1-04 [Maximum Output Frequency] and d2-01 [Frequency Reference Upper Limit] values
change.
• When A1-02 = 6, 7 [Control Method Selection = PM Advanced Open Loop Vector, PM Closed Loop Vector], the drive changes o1-03
= 1 [0.01% (100% = E1-04)].
• This parameter sets the frequency reference of Multi-Step Speed 13.