10.18 Parameters that Change from the Default Settings with A1-02 [Control Method Selection]
614 YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
10.18 Parameters that Change from the Default Settings with
A1-02 [Control Method Selection]
The values for the parameters in these tables depend on the values for parameter A1-02. Changing the setting for
A1-02 will change the default settings.
◆ A1-02 = 0 to 4 [Induction Motor Control Methods]
No. Name
Setting
Range
Unit
Control Method (A1-02 Setting)
V/f
(0)
CL-V/f
(1)
OLV
(2)
CLV
(3)
AOLV
(4)
b2-01
DC Injection/
Zero
SpeedThres
hold
0.0 - 10.0 0.1 Hz 0.5 0.5 0.5 0.5 0.5
b2-04
DC Inject
Braking Time
at Stop
0.00 - 10.00 0.01 s 0.50 0.50 0.50 0.50 0.50
b3-01
Speed Search
at Start
Selection
0 - 1 1 0 1 0 1 0
b3-14
Bi-directional
Speed Search
0 - 1 1 1 0 1 1 1
b5-15
PID Sleep
Function
Start Level
0.0 - 400.0 0.1 Hz 0.0 0.0 0.0 0.0 0.0
b6-01
Dwell
Reference at
Start
0.0 - 400.0 0.1 Hz 0.0 0.0 0.0 0.0 0.0
b6-03
Dwell
Reference at
Stop
0.0 - 400.0 0.1 Hz 0.0 0.0 0.0 0.0 0.0
b8-02
Energy
Saving Gain
0.0 - 10.0 0.1 - - 0.7 1.0 1.0
b8-03
Energy
Saving Filter
Time
0.00 - 10.00 0.01 s - - 0.50
*1
0.01
*1
0.01
*1
C1-11
Accel/Decel
Time
Switchover
Freq
0.0 - 400.0 0.1 Hz 0.0 0.0 0.0 0.0 0.0
C2-01
S-Curve
Time @ Start
of Accel
0.00 - 10.00 0.01 s 0.20 0.20 0.20 0.20 0.20
C3-01
Slip
Compensa
tion Gain
0.0 - 2.5 0.1 0.0 - 1.0 1.0 0.1
C3-02
Slip
Compensa
tion Delay
Time
0 - 10000 1 ms 2000 - 200 - -
C4-01
Torque
Compensa
tion Gain
0.00 - 2.50 0.01 1.00 1.00 1.00 - -
C4-02
Torque
Compensa
tion Delay
Time
0 - 10000 1 ms 200
*2
200
*2
20 - -
C5-01
ASR
Proportional
Gain 1
0.00 - 300.00 0.01 - 0.20 - 20.00 10.00