11.8 H: Terminal Functions
896 YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
■ H2-66: Term M5-M6 Secondary Function
No.
(Hex.)
Name Description
Default
(Range)
H2-66
(1B4C)
Expert
Term M5-M6
Secondary Function
Selects the second function for terminal M5-M6. The logical calculation
results of the terminals assigned to functions by H2-03 [Term M5-M6
Function Selection] is output.
F
(0 - A7)
■ H2-67: Terminal M5-M6 Logical Operation
No.
(Hex.)
Name Description
Default
(Range)
H2-67
(1B4D)
Expert
Terminal M5-M6
Logical Operation
Sets the logical operation for the functions set in H2-03 [Term M5-M6
Function Selection] and H2-66 [Term M5-M6 Secondary Function].
0
(0 - 8)
Note:
Refer to Output of Logical Operation Results of MFDO on page 888 for more information about the relation between parameter settings
and logical operations.
■ H2-68: Terminal M5-M6 Delay Time
No.
(Hex.)
Name Description
Default
(Range)
H2-68
(1B4E)
Expert
Terminal M5-M6
Delay Time
Sets the minimum on time used to output the logical calculation results from
terminal M5-M6.
0.1 s
(0.0 - 25.0 s)
◆ MFDO Setting Value
Selects the function configured to MFDO.
■ 0: During Run
Setting Function Description
0 During Run
The terminal activates when the Run command is input and when the drive is making voltage.
Figure 11.91 Drive Running Time Chart
ON : Drive is running
Drive is operating or making voltage.
OFF : Drive is stopping
Drive is stopped.
■ 1: Zero Speed
Setting Function Description
1 Zero Speed
The terminal activates when the output frequency is less than the value of E1-09 [Minimum Output
Frequency] or b2-01 [DC Injection/Zero SpeedThreshold].