Parameter Details
11
11.8 H: Terminal Functions
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual 895
■ H2-60: Term M1-M2 Secondary Function
No.
(Hex.)
Name Description
Default
(Range)
H2-60
(1B46)
Expert
Term M1-M2
Secondary Function
Selects the second function for terminal M1-M2. The logical calculation
results of the terminals assigned to functions by H2-01 [Term M1-M2
Function Selection] is output.
F
(0 - A7)
■ H2-61: Terminal M1-M2 Logical Operation
No.
(Hex.)
Name Description
Default
(Range)
H2-61
(1B47)
Expert
Terminal M1-M2
Logical Operation
Sets the logical operation for the functions set in H2-01 [Term M1-M2
Function Selection] and H2-60 [Term M1-M2 Secondary Function].
0
(0 - 8)
Note:
Refer to Output of Logical Operation Results of MFDO on page 888 for more information about the relation between parameter settings
and logical operations.
■ H2-62: Terminal M1-M2 Delay Time
No.
(Hex.)
Name Description
Default
(Range)
H2-62
(1B48)
Expert
Terminal M1-M2
Delay Time
Sets the minimum on time used to output the logical calculation results from
terminal M1-M2.
0.1 s
(0.0 - 25.0 s)
■ H2-63: Term M3-M4 Secondary Function
No.
(Hex.)
Name Description
Default
(Range)
H2-63
(1B49)
Expert
Term M3-M4
Secondary Function
Selects the second function for terminal M3-M4. The logical calculation
results of the terminals assigned to functions by H2-02 [Term M3-M4
Function Selection] is output.
F
(0 - A7)
■ H2-64: Terminal M3-M4 Logical Operation
No.
(Hex.)
Name Description
Default
(Range)
H2-64
(1B4A)
Expert
Terminal M3-M4
Logical Operation
Sets the logical operation for the functions set in H2-02 [Term M3-M4
Function Selection] and H2-63 [Term M3-M4 Secondary Function].
0
(0 - 8)
Note:
Refer to Output of Logical Operation Results of MFDO on page 888 for more information about the relation between parameter settings
and logical operations.
■ H2-65: Terminal M3-M4 Delay Time
No.
(Hex.)
Name Description
Default
(Range)
H2-65
(1B4B)
Expert
Terminal M3-M4
Delay Time
Sets the minimum on time used to output the logical calculation results from
terminal M3-M4.
0.1 s
(0.0 - 25.0 s)