11.7 F: Options
836 YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
■ F4-06: Terminal V2 Bias
No.
(Hex.)
Name Description
Default
(Range)
F4-06
(0396)
RUN
Terminal V2 Bias
Sets the bias of the monitor signal that is sent from terminal V2. Set the
level of the analog signal sent from the V2 terminal at 10 V or 20 mA as
100% when an output for monitoring items is 0%.
0.0%
(-999.9 - +999.9%)
The maximum output voltage output from terminal V2 is ±10 V. Use F4-08 [Terminal V2 Signal Level] to set the
signal level.
■ F4-07: Terminal V1 Signal Level
No.
(Hex.)
Name Description
Default
(Range)
F4-07
(0397)
Terminal V1 Signal
Level
Sets the output signal level for terminal V1.
0
(0, 1)
0 : 0 to 10 V
1 : -10 to 10 V
■ F4-08: Terminal V2 Signal Level
No.
(Hex.)
Name Description
Default
(Range)
F4-08
(0398)
Terminal V2 Signal
Level
Sets the output signal level for terminal V2.
0
(0, 1)
0 : 0 to 10 V
1 : -10 to 10 V
◆ F5: Digital Output Option
F5 parameters set the output mode and function of output signals when you use digital output option card DO-A3.
When you install a DO-A3 to the drive, you can output isolated digital signals to monitor the drive operation
status.
• 6 points of photocoupler output (48 V, 50 mA or less)
• 2 points of relay contact output (250 Vac, 30 Vdc: 1 A or less)
Refer to the DO-A3 option manual for more information about how to install, wire, and set the DO-A3 card.
■ Use Parameters to Select Output Modes
Use parameter F5-09 [DO-A3 Output Mode Selection] to set signal output from the DO-A3 card.