Parameter Details
11
11.7 F: Options
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual 837
Table 11.51 Details of F5-09 and the DO-A3 Terminal Output
DO-A3 Terminal Block DO-A3 Terminal Name
F5-09 = 0 [Predefined
Individual Outputs]
(Default)
F5-09 = 1 [Binary
Output]
F5-09 = 2
[Programmable (F5-01
to F5-08)]
TB1 M1-M2 Zero speed detection in
progress
During run Depending on the setting
of F5-07 [Terminal M1-
M2 Function Select]
M3-M4 During speed agreement Minor fault (excluding bb
[Baseblock])
Depending on the setting
of F5-08 [Terminal M3-
M4 Function Select]
TB2 P1-PC oC [Overcurrent], GF
[Ground Fault]
Coded output
Note:
Refer to Table 11.52
for details.
Depending on the setting
of F5-01 [Terminal P1-PC
Function Select]
P2-PC ov [Overvoltage] Depending on the setting
of F5-02 [Terminal P2-PC
Function Select]
P3-PC oL2 [Drive Overload] or
oH2 [Heatsink Overheat]
Depending on the setting
of F5-03 [Terminal P3-PC
Function Select]
P4-PC Not used Depending on the setting
of F5-04 [Terminal P4-PC
Function Select]
P5-PC oS [Overspeed] Zero speed detection in
progress
Depending on the setting
of F5-05 [Terminal P5-PC
Function Select]
P6-PC oH, oH1 [Heatsink
Overheat] or oL1 [Motor
Overload]
During speed agreement Depending on the setting
of F5-06 [Terminal P6-PC
Function Select]
Table 11.52 Binary Output [F5-09 = 1]
Coded Output
(Binary)
Description
DO-A3 Terminal Block TB2
Terminal P1-PC Terminal P2-PC Terminal P3-PC Terminal P4-PC
0 No fault 0 0 0 0
1 oC [Overcurrent], GF
[Ground Fault]
1 0 0 0
2 ov [Overvoltage] 0 1 0 0
3 oL2 [Drive
Overloaded]
1 1 0 0
4 oH, oH1 [Heatsink
Overheat]
0 0 1 0
5 oS [Overspeed] 1 0 1 0
6 Not used 0 1 1 0
7 rr [Dynamic Braking
Transistor Fault], rH
[Braking Resistor
Overheat]
1 1 1 0
8 External fault [EF1 to
EF8]
0 0 0 1
9 CPFxx, oFAxx,
oFbxx, oFCxx [Drive
Hardware Fault]
*1
1 0 0 1
A oL1 [Motor
Overload]
0 1 0 1
B Not used 1 1 0 1
C Uv1, Uv2
[Undervoltage], Uv3
[Soft Charge
Answerback Fault]
0 0 1 1
D dEv [Speed
Deviation]
1 0 1 1