Parameter Details
11
11.11 o: Keypad-Related Settings
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual 1017
o1-50: Trend Plot 2 Scale Maximum Value
No.
(Hex.)
Name Description
Default
(Range)
o1-50
(11CA)
RUN
Trend Plot 2 Scale
Maximum Value
Sets the maximum value for the vertical axis used to display the monitor
that was set in o1-25 [Custom Monitor 2] as a trend plot. This parameter
is only available with an LCD keypad.
100.0%
(-99.9 - +300.0%)
o1-51: Trend Plot Time Scale Setting
No.
(Hex.)
Name Description
Default
(Range)
o1-51
(11CB)
RUN
Trend Plot Time
Scale Setting
Sets the time scale (horizontal axis) to display the trend plot. When you
change this setting, the drive automatically adjusts the data sampling time.
This parameter is only available with an LCD keypad.
300 s
(1 - 3600 s)
o1-55: Analog Gauge Area Selection
No.
(Hex.)
Name Description
Default
(Range)
o1-55
(11EE)
RUN
Analog Gauge Area
Selection
Sets the range used to display the monitor set in o1-24 [Custom Monitor 1]
as an analog gauge. This parameter is only available with an LCD keypad.
1
(0, 1)
0 : +/- Area ( - o1-56 o1-56 )
1 : + Area ( 0 o1-56 )
o1-56: Analog Gauge Area Setting
No.
(Hex.)
Name Description
Default
(Range)
o1-56
(11EF)
RUN
Analog Gauge Area
Setting
Sets the value used to display the monitor set in o1-24 [Custom Monitor 1]
as an analog meter. This parameter is only available with an LCD keypad.
100.0%
(0.0 - 100.0%)
o2: Keypad Operation
o2-01: LO/RE Key Function Selection
No.
(Hex.)
Name Description
Default
(Range)
o2-01
(0505)
LO/RE Key Function
Selection
Sets the function that lets the drive switch between LOCAL and REMOTE
Modes using the button.
1
(0, 1)
0 : Disabled
You cannot use to switch between LOCAL and REMOTE Modes.
1 : Enabled
You can use to switch between LOCAL and REMOTE Modes when the drive is stopped. When LOCAL
Mode is selected, on the keypad will come on.
WARNING! Sudden Movement Hazard. The drive may start unexpectedly if switching control sources when setting b1-07 = 1
[LOCAL/REMOTE Run Selection = Accept Existing RUN Command]. Clear all personnel from rotating machinery and electrical
connections prior to switching control sources. Failure to comply may cause death or serious injury.
WARNING! Sudden Movement Hazard. Fully examine all mechanical and electrical connections before you change o2-01 [LO/
RE Key Function Selection] or b1-07 [LOCAL/REMOTE Run Selection]. If b1-07 = 1 [Accept Existing RUN Command] and there
is an active Run command when you switch from LOCAL to REMOTE Mode, the drive can start suddenly. Failure to obey can
cause serious injury or death.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV