11.11 o: Keypad-Related Settings
1018 YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
Table 11.77 Function Settings via o2-01 through b1-07
Function Selection
LOCAL/REMOTE Run
Selection
Switching from LOCAL
Mode to REMOTE Mode
Switching from REMOTE
Mode to LOCAL Mode
o2-01 = 0 [Disabled] b1-07 = 0 [Disregard Existing
RUN Command]
The drive will not switch modes. The drive will not switch modes.
b1-07 = 1 [Accept Existing RUN
Command]
o2-01 = 1 [Enabled] b1-07 = 0 [Disregard Existing
RUN Command]
The drive will not start operating
although the Run command is
active. When you set Run
command to active again, the
drive will start to run.
The drive cannot operate because
the Run command is not enabled.
b1-07 = 1 [Accept Existing RUN
Command]
When the Run command is
active, the drive will start to run
immediately when the mode
switches from LOCAL to
REMOTE.
The drive cannot operate because
the Run command is not enabled.
■ o2-02: STOP Key Function Selection
No.
(Hex.)
Name Description
Default
(Range)
o2-02
(0506)
STOP Key Function
Selection
Sets the function to stop the drive with the button on the keypad
when the Run command source for the drive is REMOTE (external) and not
assigned to the keypad.
1
(0, 1)
0 : Disabled
1 : Enabled
stays enabled when the Run command source has not been assigned to the keypad.
To start the drive again after you push to stop operation, turn the external Run command OFF and ON
again.
■ o2-03: User Parameter Default Value
No.
(Hex.)
Name Description
Default
(Range)
o2-03
(0507)
User Parameter
Default Value
Sets the function to keep the settings of changed parameters as user
parameter defaults to use during initialization.
0
(0 - 2)
When you set this parameter to 1, the drive saves changed parameter settings as user parameter setting values in a
part of the memory that is isolated from drive parameters.
When you set A1-03 = 1110 [Initialize Parameters = User initialization] to initialize the drive, the drive resets the
internal parameter setting values to those user parameter setting values.
0 : No change
1 : Set defaults
Saves changed parameter settings as user-set default for User Initialization.
Set o2-03 = 1 [Set defaults], then push on the keypad to save the user parameter setting values. After the drive
saves the setting value, o2-03 automatically resets to 0.
2 : Clear all
Deletes all of the saved user parameter setting values.
To delete the user parameter setting values, set this parameter to 2 and push on the keypad. The drive will
automatically reset o2-03 to 0. If you delete the user parameter setting values, you cannot set A1-03 = 1110 to
initialize parameters.