6.6 Parameter Setting Errors
374 YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
6.6 Parameter Setting Errors
Parameter setting errors occur when multiple parameter settings do not agree, or when parameter setting values
are not correct. Refer to the table in this section, examine the parameter setting that caused the error, and remove
the cause of the error. You must first correct the parameter setting errors before you can operate the drive. The
drive will not send notification signals for the faults and alarms when these parameter setting errors occur.
Code Name Causes Possible Solutions
oPE01 Drive Capacity Setting
Error
The value set in o2-04 [Drive Model
(KVA) Selection] does not agree with the
drive model.
Set o2-04 to the correct value.
Code Name Causes Possible Solutions
oPE02 Parameter Range Setting
Error
Parameters settings are not in the
applicable setting range.
1. Push to show U1-18 [oPE Fault
Parameter], and find parameters that are not in
the applicable setting range.
2. Correct the parameter settings.
Note:
If more than one error occurs at the same time,
other oPExx errors have priority over oPE02.
Set E2-01 ≤ E2-03 [Motor Rated
Current (FLA) ≤ Motor No-Load
Current].
Make sure that E2-01 > E2-03.
Note:
If it is necessary to set E2-01 < E2-03, first
lower the value set in E2-03, and then set E2-
01.
Code Name Causes Possible Solutions
oPE03 Multi-Function Input
Setting Err
The settings for these parameters do not
agree:
• H1-01 to H1-08 [Terminal S1 to S8
Function Selection]
• F3-10 to F3-25 [Terminal D1 to DF
Function Selection]
• H7-01 to H7-04 [Virtual Multi-
Function Inputs 1 to 4]
Set the parameters correctly.
The settings for the standby mode
function do not agree:
• b8-50 = 0 [Standby Mode Selection =
Disabled] and H2-xx = 65 [MFDO
Function Select = Standby Output]
• b8-50 = 1 [Enabled] and H2-xx ≠ 65
Set the parameters correctly.
The settings for MFDIs overlap.
Note:
This does not include H1-xx = 20 to
2F [MFDI Function Select =
External Fault] and [Reserved].
Set the parameters correctly to prevent MFDI
function overlap.
These pairs of MFDI functions are not
set to Digital Inputs (H1-xx, F3-10 to
F3-25, and H7-01 to H7-04) at the same
time:
• Setting values 10 [Up Command] and
11 [Down Command]
• Setting values 75 [Up 2 Command]
and 76 [Down 2 Command]
• Setting values 42 [Run Command (2-
Wire Sequence 2)] and 43 [FWD/REV
(2-Wire Sequence 2)]
Set the MFDI pairs.