YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual 811
E3-11: Motor 2 Mid Point B Frequency
No.
(Hex.)
Name Description
Default
(Range)
E3-11
(0345)
Expert
Motor 2 Mid Point B
Frequency
Sets a middle output frequency for the motor 2 V/f pattern. Set this
parameter to adjust the V/f pattern for the constant output range. Usually it
is not necessary to change this setting.
0.0 Hz
(0.0 - E3-04)
Note:
Set this parameter to 0.0 to disable the function.
When you initialize the drive, this parameter is reset to the default value.
E3-12: Motor 2 Mid Point B Voltage
No.
(Hex.)
Name Description
Default
(Range)
E3-12
(0346)
Expert
Motor 2 Mid Point B
Voltage
Sets a middle output voltage for the motor 2 V/f pattern. Set this parameter
to adjust the V/f pattern for the constant output range. Usually it is not
necessary to change this setting.
0.0 V
(200 V Class: 0.0 -
255.0 V, 400 V Class:
0.0 - 510.0 V)
Note:
Set this parameter to 0.0 to disable the function.
When you initialize the drive, this parameter is reset to the default value.
The setting value changes automatically when you do Auto-Tuning (rotational and stationary 1 or 2).
E3-13: Motor 2 Base Voltage
No.
(Hex.)
Name Description
Default
(Range)
E3-13
(0347)
Expert
Motor 2 Base Voltage
Sets the base voltage for the motor 2 V/f pattern. Set this parameter to adjust
the V/f pattern for the constant output range. Usually it is not necessary to
change this setting.
0.0 V
(200 V Class: 0.0 -
255.0 V, 400 V Class:
0.0 - 510.0 V)
Note:
When you initialize the drive, this parameter is reset to the default value.
The setting value changes automatically when you do Auto-Tuning (rotational and stationary 1 or 2).
E4: Motor 2 Parameters
E4 parameters [Motor 2 Parameters] set induction motor data. To switch drive operation from one motor to a
different motor, configure motor 2.
Auto-Tuning automatically sets the E4 parameters to the best values for the application. If you cannot do Auto-
Tuning, set the E4 parameters manually.
Note:
E3-xx and E4-xx are available when H1-xx = 16 [MFDI Function Select = Motor 2 Selection].
E4-01: Motor 2 Rated Current
No.
(Hex.)
Name Description
Default
(Range)
E4-01
(0321)
Motor 2 Rated
Current
Sets the motor rated current for motor 2 in amps.
Determined by o2-04
and C6-01
(10% to 200% of the
drive rated current)
Note:
If E4-01 E4-03 [Motor 2 Rated No-Load Current], the drive will detect oPE02 [Parameter Range Setting Error] will be detected.
The default settings and setting ranges are in these units:
0.01 A: 2004 to 2042, 4002 to 4023
0.1 A: 2056 to 2415, 4031 to 4675
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV

Table of Contents

Other manuals for YASKAWA GA700

Related product manuals